EasyManua.ls Logo

IDEC SmartAXIS Touch FT1A Series

IDEC SmartAXIS Touch FT1A Series
1232 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SmartAXIS Touch User's Manual 27-9
2 Word Devices
27
Internal Devices
2.1 HMI Device Addresses
HMI Data Register (LDR)
8,192 points are available.
HMI Keep Register (LKR)
The value in these registers is retained during power OFF.
The maximum number of HMI Keep Register depends upon the number set in WindO/I-NV3. For details, refer to
Chapter 16 “Minimum and Maximum Amount of Data Storage and Number of Addresses” on page 16-2.
HMI Temporary Register (LBR)
This register value will be cleared to 0 when a text group or user account is changed, when a screen is reset or the
screen is changed. 128 points are available.
HMI Timer (Current value) (LTD)
HMI Timer stores the current value of Timer from the parts. 32 points are available.
HMI Special Data Register (LSD)
The HMI Special
Data Registers (256 points) perform the following special operations.
2Word Devices
Internal Device Name Symbol R/W Address Range Base
HMI Data Register LDR R/W 0 to 8191 10
HMI Keep Register LKR R/W Variable 10
HMI Temporary Register LBR R/W 0 to 127 10
HMI Timer (Current) LTD R 0 to 31 10
HMI Special Data Register LSD R/W 0 to 255 10
R/W stands for Read/Write. R/W enables reading and writing of values, whereas R enables reading only.
Address Function/Part
LSD0 to 3
Reserved
LSD4 Scan time Maximum value of the Touch (msec)
LSD5 Screen switch response time (msec)
LSD6 Read scan communication time (msec)
LSD7 Scan counter (incremented at each scan of the Touch)
LSD8 1 second counter (incremented each second)
LSD9 10 millisecond counter (increments every 10 msec)
LSD10 100 millisecond counter (incremented every 100 msec)
LSD11 200 millisecond counter (incremented every 200 msec)
LSD12 500 millisecond counter (incremented every 500 msec)
LSD13 Stores the current Year data from the Touch. “Year” (4 BCD digits)
LSD14 Stores current time data from Touch. “Month” (2 BCD digits)
LSD15 Stores current time data from Touch. “Day” (2 BCD digits)
LSD16 Stores current time data from Touch. “Hour” (2 BCD digits)
LSD17 Stores current time data from Touch. “Minute” (2 BCD digits)
LSD18 Stores current time data from Touch. “Second” (2 BCD digits)
LSD19 Stores current time data from Touch. “Day-of-week” (1 BCD digit)

Table of Contents

Related product manuals