1 Bit Devices
27-4 SmartAXIS Touch User's Manual
1.2 Control Device Addresses
â– Input (I)
Inputs (I) are relays to receive input signals through the input terminals.
â– Output (Q)
Outputs (Q) are relays to send the processed results to the output terminals.
â– Remote Input (I)
Remote inputs (I) are devices to input the on/off state from external devices connected to remote I/O slaves to the
Touch.
â– Remote Output (Q)
Remote outputs (Q) are devices to output the on/off information from the Touch to external devices connected to
remote I/O slaves.
â– Timer (T)
Control device timers are bit unit devices that become 1 when the time is up.
â– Counter (C)
Control device counters are bit unit devices that become 1 when the count is up.
â– Shift registers (R)
Shift registers (R) are registers to shift the data bits according to pulse inputs.
â– Internal Relay (M)
Internal relays (M) are relays used in the Touch and cannot be outputted to the output terminals.
*1 The last digit of the device address is 0 to 7 in octal notation.
Internal Device Name Symbol R/W Address Range Base
Input I R 0 to 7 8
Output Q R/W 0 to 3 8
Remote Input I R
40 to 75
80 to 115
120 to 155
8
Remote Output Q R/W
40 to 61
80 to 101
120 to 141
8
Timer Bit T R 000 to 199 10
Counter Bit C R 000 to 199 10
Shift Register R R/W 0 to 127 10
Internal Relay M R/W 0 to 1277
10
*1
Special Internal Relay M R/W 8000 to 8177
10
*1
R/W stands for Read/Write. R/W enables reading and writing of values, whereas R enables reading only.
• Control devices must have a "#" before the device type only when the WindO/I-NV3 is used.
In addition, on the Device Monitor a "#" is displayed before the device type.
Example: When setting D100
WindO/I-NV3: #D100
WindLDR: D100
• Values can only be written from the HMI function to outputs (Q) while the ladder program or FBD program is
running.
• Do not simultaneously write values to the same control device using the HMI function and the control function.
• Operations in scripts of control function are as follows.
- Bit of Data register can be handled as a bit device.
- Calculations in which both bit and word devices are used are not allowed.
- Bit devices are always processed as bits, and values of those devices are 0(OFF) or 1(ON).