SmartAXIS Touch User's Manual 3-33
3 Project Settings Dialog Box
3
Project
■ Ignore communication errors and continue operation
Select this check box to continue Touch operation even when a communication error occurs.
This option is only displayed when the communication driver Connection is 1:N Communication.
Display error message: Select this check box to display an error message (communication error) when a
communication error occurs and operation continues. Ack is displayed on the error
message (communication error).
When the Ignore communication errors and continue operation check box is
cleared, Ack is not displayed on the error message.
Auto retry: Select this check box to automatically retry communication from the Touch to the station
number where the communication error occurred when a communication error occurs
and operation continues.
All other communication stops while retrying.
To manually retry communication, clear the Auto retry check box.
To retry all station numbers, write 1 in bit 1 (initialize) of the device address configured by Batch
monitoring the communication error information for all Station Numbers.
To individually retry communication, write 1 in bit 0 (connection setting) of the device address configured by
Monitoring communication error information for each station number, individually.
Batch monitoring the communication error information for all Station Numbers:
Specifies the device that stores communication error information for all station numbers.
Only the HMI devices can be configured for this option.
Click to display the Device Address Settings dialog box. For the device address
configuration procedure, refer to Chapter 2 “5.1 Device Address Settings” on page 2-62.
The information stored as error information is as follows. For details, refer to the
"External Device Setup Manual".
• Initialization
• Conditions under which the error occurred
• Read error log
• Write error log
Monitoring communication error information for each station number, individually:
Specifies the device that stores communication error information for each station
number. Only the HMI devices can be configured for this option.
Click to display the Device Address Settings dialog box. For the device address
configuration procedure, refer to Chapter 2 “5.1 Device Address Settings” on page 2-62.
This error information utilizes a maximum of 256 devices. Use caution so that the used
addresses do not overlap with other addresses.
The information stored as error information is as follows. For details, refer to the
"External Device Setup Manual".
• Connection settings
• Conditions under which the error occurred
• Read error log
• Write error log