SmartAXIS Touch User's Manual 3-71
4 Special Functions
3
Project
Program
M8120 (initialize pulse) is a special internal relay that turns on for one scan when the Touch runs.
Preset value 1=2,700
2,700 pulses
Perforation time: 0.5 seconds
Q2
M8031
M8031
M8032
M8030
M0000
M0000
M0000
M8120
Current value
Reset value 0
Comparison output Q2
M8120
SOTU
SOTD
D1-
D0004
REPS1-
2700
MOV(D)
D1-
D8054
REPS1-
0
MOV(D)
D1-
D0002
REPS1-
1
MOV(W)
TIM
5
T0
1st scan
Store 2,700 in preset value 1 (D0004, D0005)
3rd scan
Detect the rising edge of M0000, turn on gate input (M8031)
Start high-speed counter counting in the END processing after the 3rd
scan is executed
2nd scan
Detect the falling edge of the initialize pulse, M0000 and M8032 turn on
Initialize the current value with the reset value in the END processing
after the 2nd scan is executed
Store 0 in the reset value (D8054, D8055)
Turn off gate input (M8031)
Turn off M0000
M8032 (reset input) is a special internal relay that stores the reset
value (D8054, D8055) in the current value (D8050, D8051).
When the current value becomes 2,700 pulses, comparison
output Q2 turns on
The timer starts and comparison output reset (M8030) turns on after
five seconds
Store 1 in the next preset value number (D0002)
In this example, Z-phase reset input is not used.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IDEC SmartAXIS Touch FT1A Series and is the answer not in the manual?

IDEC SmartAXIS Touch FT1A Series Specifications

General IconGeneral
BrandIDEC
ModelSmartAXIS Touch FT1A Series
CategoryController
LanguageEnglish

Related product manuals