Parameters
List of parameters
1-106
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Description: Defines the rated overtemperature of the squirrel cage rotor referred to ambient temperature.
Dependency: For 1LA7 motors (p0300), the parameter is pre-set as a function of p0307 and p0311.
Refer to: p0625
Caution: When selecting a standard induction motor listed in the catalog (p0300 > 100, p0301 > 10000), this parameter is
automatically preassigned and is write protected. Information in p0300 should be carefully observed when removing
write protection.
Note: When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
Description: Displays the ambient temperature of the motor temperature model.
Description: Displays the stator core temperature of the motor temperature model.
Description: Displays the stator winding temperature of the motor temperature model.
Description: Displays the rotor temperature of the motor temperature model.
Note: For motor temperature model 3 (p0612.2 = 1), this parameter is not valid:
p0628[0...n] Motor overtemperature rotor winding / Mot T_over rotor
Access level: 4 Calculated: p0340 = 1,2 Data type: FloatingPoint32
Can be changed: C(3), U, T Scaling: - Dyn. index: MDS
Units group: 21_2 Unit selection: p0505 Func. diagram: 8016
Min Max Factory setting
20 [K] 200 [K] 100 [K]
r0630[0...n] Mot_temp_mod ambient temperature / Mod T_ambient
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2006 Dyn. index: MDS
Units group: 21_1 Unit selection: p0505 Func. diagram: 8016
Min Max Factory setting
- [°C] - [°C] - [°C]
r0631[0...n] Mot_temp_mod stator iron temperature / Mod T_stator
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2006 Dyn. index: MDS
Units group: 21_1 Unit selection: p0505 Func. diagram: 8016
Min Max Factory setting
- [°C] - [°C] - [°C]
r0632[0...n] Mot_temp_mod stator winding temperature / Mod T_winding
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2006 Dyn. index: MDS
Units group: 21_1 Unit selection: p0505 Func. diagram: 8016
Min Max Factory setting
- [°C] - [°C] - [°C]
r0633[0...n] Mot_temp_mod rotor temperature / Mod T_rotor
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2006 Dyn. index: MDS
Units group: 21_1 Unit selection: p0505 Func. diagram: 8016
Min Max Factory setting
- [°C] - [°C] - [°C]