List of parameters
Parameters
1-319
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Note: The function can only be activated using a 0/1 signal if no reference function is active (r2526.2).
If "reference mark search" and "measuring probe evaluation" are simultaneously activated, then no function is acti-
vated and the actual function is interrupted.
Description: Sets the signal source for the function "activating the measuring probe evaluation".
0/1 signal: The function "activate measuring probe evaluation" is started.
Index: [0] = Cl-loop pos ctrl
[1] = Encoder 1
[2] = Encoder 2
[3] = Reserved
Dependency: Refer to: p0488, p0489, p0490, p2502, p2508, p2510, p2511, p2517, p2518
Refer to: A07495
Notice: When the "set position actual value" is activated while the function "measuring probe evaluation" is activated, then
the function "measuring probe evaluation" is automatically de-activated.
Note: The function can only be activated using a 0/1 signal if no reference function is active (r2526.2).
If "reference mark search" and "measuring probe evaluation" are simultaneously activated, then no function is acti-
vated and the actual function is interrupted.
Description: Sets the signal source to select the measuring probe.
1 signal = measuring probe 2 is activated for BI: p2509 = 0/1 edge.
0 signal = measuring probe 1 is activated for BI: p2509 = 0/1 edge.
Index: [0] = Cl-loop pos ctrl
[1] = Encoder 1
[2] = Encoder 2
[3] = Reserved
Dependency: Refer to: p2502, p2509, p2511
Note: The following BICO interconnection is established as standard:
BI: p2509[0] = r2684.1
The measuring probe is selected at the 0/1 signal transition at r2684.1 (flying referencing active).
p2509[0...3] BI: LR activating measuring probe evaluation / MT_eval act
CU250D-2_DP_F
CU250D-2_PN_F
Access level: 1 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 4010
Min Max Factory setting
- - [0] 2684.1
[1] 0
[2] 0
[3] 0
p2510[0...3] BI: LR selecting measuring probe evaluation / MT_eval select
CU250D-2_DP_F
CU250D-2_PN_F
Access level: 1 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 3615, 4010
Min Max Factory setting
- - 0