Description: Sets the flux setpoint referred to rated motor flux.
Notice: A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note: For p1570 > 100%, the flux setpoint increases as a function of the load from 100% (no-load operation) to the setting
in p1570 (above rated motor torque), if p1580 > 0% has been set.
Description: Sets the flux threshold value for enabling the speed setpoint and the end of magnetizing (r0056.4).
Note: The parameter only has an influence if the flux actual value reaches the threshold value p1573 more quickly during
magnetizing than the time set in p0346.
The parameter has no influence for flying restart (see p1200) and after DC braking (see p1231).
Description: Sets a dynamic voltage reserve.
Dependency: Refer to: p0500
Note: In the field weakening range, it must be expected that the control dynamic performance is somewhat restricted due
to the limited possibilities of controlling/adjusting the voltage. This can be improved by increasing the voltage
reserve. Increasing the reserve reduces the steady-state maximum output voltage (r0071).
Description: Sets the efficiency optimization.
When optimizing the efficiency, the flux setpoint of the closed-loop control is adapted as a function of the load.
For p1580 = 100 %, under no-load operating conditions, the flux setpoint is reduced to 50 % of the rated motor flux.
Note: It only makes sense to activate this function if the dynamic response requirements of the speed controller are low.
In order to avoid oscillations, if required, the speed controller parameters should be adapted (increase Tn, reduce
Kp).
Further, the smoothing time of the flux setpoint filter (p1582) should be increased.
p1570[0...n] CO: Flux setpoint / Flex setp
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 6722
Min Max Factory setting
50.0 [%] 200.0 [%] 100.0 [%]
p1573[0...n] Flux threshold value magnetizing / Flux thresh magnet
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 6722
Min Max Factory setting
10.0 [%] 200.0 [%] 100.0 [%]
p1574[0...n] Voltage reserve dynamic / U_reserve dyn
Access level: 3 Calculated: p0340 = 1,3,5 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: 5_1 Unit selection: p0505 Func. diagram: 6723, 6724
Min Max Factory setting
0.0 [Vrms] 150.0 [Vrms] 10.0 [Vrms]
p1580[0...n] Efficiency optimization / Efficiency opt.
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 6722
Min Max Factory setting
0 [%] 100 [%] 0 [%]