Parameters
List of parameters
1-312
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Description: Sets the signal source to hold the integrator for the technology controller.
Description: Sets the signal source for the pre-control signal of the technology controller.
Description: Sets the maximum limit of the technology controller.
Dependency: Refer to: p2292
Caution: The maximum limit must always be greater than the minimum limit (p2291 > p2292).
Description: Sets the minimum limit of the technology controller.
Dependency: Refer to: p2291
Caution: The maximum limit must always be greater than the minimum limit (p2291 > p2292).
p2286[0...n] BI: Hold technology controller integrator / Tec_ctr integ stop
CU240D-2_DP
CU240D-2_DP_F
CU240D-2_PN
CU240D-2_PN_F
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 7958
Min Max Factory setting
- - 56.13
p2289[0...n] CI: Technology controller pre-control signal / Tec_ctrl prectrl
CU240D-2_DP
CU240D-2_DP_F
CU240D-2_PN
CU240D-2_PN_F
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 7958
Min Max Factory setting
- - 0
p2291 CO: Technology controller maximum limiting / Tec_ctrl max_lim
CU240D-2_DP
CU240D-2_DP_F
CU240D-2_PN
CU240D-2_PN_F
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7958
Min Max Factory setting
-200.00 [%] 200.00 [%] 100.00 [%]
p2292 CO: Technology controller minimum limiting / Tec_ctrl min_lim
CU240D-2_DP
CU240D-2_DP_F
CU240D-2_PN
CU240D-2_PN_F
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7958
Min Max Factory setting
-200.00 [%] 200.00 [%] 0.00 [%]