Description: Status display for the PROFIBUS interface.
Value: 0: OFF
1: No connection (search for baud rate)
2: Connection OK (baud rate found)
3: Cyclic connection with master (data exchange)
4: Cyclic data OK
Description: Diagnostics display for the PROFIBUS interface.
Index: [0] = Master bus address
[1] = Master input total length bytes
[2] = Master output total length bytes
Description: Displays the setting of the PROFIBUS address switch "DP ADDRESS" on the Control Unit.
Dependency: Refer to: p0918
Description: Connector output to interconnect PZD (setpoints) with double word format received from the fieldbus controller.
Index: [0] = PZD 1 + 2
[1] = PZD 2 + 3
[2] = PZD 3 + 4
[3] = PZD 4 + 5
[4] = PZD 5 + 6
[5] = PZD 6 + 7
08 Bit 8 ON OFF -
09 Bit 9 ON OFF -
10 Bit 10 ON OFF -
11 Bit 11 ON OFF -
12 Bit 12 ON OFF -
13 Bit 13 ON OFF -
14 Bit 14 ON OFF -
15 Bit 15 ON OFF -
r2054 PROFIBUS status / PB status
CU240D-2_DP
CU240D-2_DP_F
CU250D-2_DP_F
Access level: 3 Calculated: - Data type: Integer16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 2410
Min Max Factory setting
0 4 -
r2055[0...2] PROFIBUS diagnostics standard / PB diag standard
CU240D-2_DP
CU240D-2_DP_F
CU250D-2_DP_F
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 2410
Min Max Factory setting
- - -
r2057 PROFIBUS address switch diagnostics / PB addr_sw diag
CU240D-2_DP
CU240D-2_DP_F
CU250D-2_DP_F
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 2410
Min Max Factory setting
- - -
r2060[0...10] CO: PROFIdrive PZD receive double word / PZD recv DW
Access level: 3 Calculated: - Data type: Integer32
Can be changed: - Scaling: 4000H Dyn. index: -
Units group: - Unit selection: - Func. diagram: 2440, 2468
Min Max Factory setting
- - -