Description: Sets the switch-off delay time for the negated signal "run-up completed".
The message "torque setpoint < p2174" (BO: r2198.10) and "torque utilization < p2194" (BO: r2199.11) are only
evaluated after the run-up and the delay time has expired.
Dependency: Refer to: p2174, p2194
Description: Sets the scaling factor for torque utilization (r0033).
Description: Displays the first status word for monitoring functions.
Notice: Re bit 06:
When the overspeed is reached, this bit is set and F07901 output immediately following this. The bit is canceled
again as soon as the next pulse inhibit is present.
Note: Re bit 00:
The threshold value is set in p1080 and the hysteresis in p2150.
Re bit 01, 02:
The threshold value is set in p2155 and the hysteresis in p2140.
Re bit 03:
1 signal direction of rotation positive.
0 signal: direction of rotation negative.
The hysteresis is set in p2150.
p2195[0...n] Torque utilization switch-off delay / M_util t_off
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 8012
Min Max Factory setting
0.0 [ms] 1000.0 [ms] 800.0 [ms]
p2196[0...n] Torque utilization scaling / M_util scal
Access level: 1 Calculated: - Data type: FloatingPoint32
Can be changed: C(1, 3), U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.00 [%] 1000.00 [%] 100.00 [%]
r2197.0...13 CO/BO: Status word monitoring 1 / ZSW monitor 1
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 1530, 2534
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 |n_act| <= n_min p1080 Yes No 8020
01 |n_act| <= speed threshold value 2 p2155 Yes No 8010
02 |n_act| > speed threshold value 2 p2155 Yes No 8010
03 n_act >= 0 Yes No 8011
04 |n_act| >= n_set Yes No 8020
05 |n_act| <= n_standstill p1226 Yes No 8020
06 |n_act| > n_max Yes No 8010
07 Speed setp - act val deviation in tolerance
t_off
Yes No 8011
08 I_act >= I_threshold value p2170 Yes No 8020
09 Vdc_act <= Vdc_threshold value p2172 Yes No 8020
10 Vdc_act > Vdc_threshold value p2172 Yes No 8020
11 Output load is not present Yes No 8020
12 |n_act| > n_max (delayed) Yes No 8021
13 |n_act| > n_max (F07901) Yes No -