Faults and alarms
List of faults and alarms
3-812
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
A02063 Trace: Invalid data type
Reaction: NONE
Acknowledge: NONE
Cause: The specified data type to select a signal using a physical address is invalid.
Remedy: Use a valid data type.
A02070 Trace: Parameter cannot be changed
Reaction: NONE
Acknowledge: NONE
Cause: The trace parameter settings cannot be changed when the trace is active.
Remedy: - stop the trace before parameterization.
- if required, start the trace.
A02075 Trace: Pretrigger time too long
Reaction: NONE
Acknowledge: NONE
Cause: The selected pretrigger time must be shorter than the trace time.
Remedy: Check the pretrigger time setting and change if necessary.
F02080 Trace: Parameterization deleted due to unit changeover
Reaction: NONE
Acknowledge: IMMEDIATELY
Cause: The trace parameterization in the drive unit was deleted due to a unit changeover or a change in the reference
parameters.
Remedy: Restart trace.
A02097 MTrace: multiple trace cannot be activated
Reaction: NONE
Acknowledge: NONE
Cause: The following functions or settings are not permissible in conjunction with a multiple trace:
- measuring function.
- long-time trace
- trigger condition "immediate recording start" (IMMEDIATE)
- trigger condition "start with function generator" (FG_START).
Remedy: - Deactivate multiple trace.
- Deactivate function or setting that is not permissible.
A02098 MTrace: cannot be saved
Reaction: NONE
Acknowledge: NONE
Cause: It is not possible to save the measurement results of a multiple trace on the memory card.
A multiple trace is not started or is canceled.
Alarm value (r2124, interpret decimal):
1: memory card cannot be accessed (not inserted or blocked by a mounted USB drive).
3: data save operation to slow. A second trace has been completed before the measurement results of the first trace
were able to be saved.
4: data save operation canceled (e.g. a file required for the save operation was no longer able to be found).
Remedy: - insert or remove the memory card.
- use a larger memory card.
- configure the trace with a longer trace time or use an endless trace.
- avoid saving parameters while the multiple trace is running. Saving parameters can
Block writing measurement result files to the card, so that this alarm is output with alarm value 3
- check whether other functions are presently accessing measurement result files of the multiple trace.