EasyManua.ls Logo

Siemens SINAMICS G120D - p9700 SI copy function; SI copy function; p9701 Acknowledge SI data change; Ackn SI data; p9705 BI: SI Motion: Test stop signal source; SI Mtn test stop

Siemens SINAMICS G120D
910 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of parameters
Parameters
1-429
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Description: Setting to start the required copy function.
After starting, the corresponding parameters are copied from processor 1 to processor 2.
Once copying is complete, the parameter is automatically reset to zero.
Value: 0: [00 hex] Copy function ended
29: [1D hex] Start copy function node identifier
87: [57 hex] Start copy function SI parameters
208: [D0 hex] Start copy function SI basic parameters
Dependency: Refer to: r3996
Notice: When the parameters are copied, short-term communication interruptions may occur.
Note: Re value = 57 hex and D0 hex:
The value can only be set if the safety commissioning mode is set and the Safety Integrated password was entered.
Re value = D0 hex:
The following parameters are copied after starting the copy function:
p9601 --> p9801, p9610 --> 9810, p9650 --> p9850, p9651 --> p9851
Description: Setting to transfer the reference checksums from the associated actual checksums after changes (SI parameters,
hardware).
After transferring the reference checksums, parameters are automatically reset to zero.
Value: 0: [00 hex] Data unchanged
172: [AC hex] Acknowledge data change complete
220: [DC hex] Acknowledge SI basic parameter change
236: [EC hex] Acknowledge hardware CRC
Dependency: Refer to: r9398, p9399, r9728, p9729, r9798, p9799, r9898, p9899
Note: Re value = AC and DC hex:
These values can only be set if the safety commissioning mode is set and the Safety Integrated password was
entered.
Description: Sets the signal source for the test stop of the safety-relevant motion monitoring functions.
p9700 SI copy function / SI copy function
Access level: 3 Calculated: - Data type: Integer16
Can be changed: C(95), U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0000 hex 00D0 hex 0000 hex
p9701 Acknowledge SI data change / Ackn SI data
Access level: 3 Calculated: - Data type: Integer16
Can be changed: C(95), U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0000 hex 00EC hex 0000 hex
p9705 BI: SI Motion: Test stop signal source / SI Mtn test stop
CU240D-2_DP_F
CU240D-2_PN_F
CU250D-2_DP_F
CU250D-2_PN_F
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: C(95) Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 2837
Min Max Factory setting
- - 0

Table of Contents

Other manuals for Siemens SINAMICS G120D

Related product manuals