Siemens SINAMICS G120D - p1730[0...n] Isd controller integral component shutdown threshold; Isd_ctr I_compDeac; p1731[0...n] Isd controller combination current time component; Isd ctrl iCombi T1; r1732[0...1] CO: Direct-axis voltage setpoint; Direct U set; r1733[0...1] CO: Quadrature-axis voltage setpoint; Quad U set

Siemens SINAMICS G120D
910 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of parameters
1-222
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Description: Sets the speed threshold for deactivating the integral component of the Isd controller. The d current controller is
only effective as P controller for speeds greater than the threshold value. Instead of the integral component, the
quadrature arm decoupling is effective.
Warning: For settings above 80%, the d current controller is active up to the field weakening limit. When operated at the volt-
age limit, this can result in an unstable behavior. In order to avoid this, the dynamic voltage reserve p1574 should
be increased.
Note: The parameter value is referred to the synchronous rated motor speed.
Description: Sets the time constant to calculate the d current DC component difference (combination current) to add to the d cur-
rent controller actual value. The additional input is de-activated with p1731 = 0.
Description: Displays the direct-axis voltage setpoint Ud.
Index: [0] = Unsmoothed
[1] = Smoothed with p0045
Description: Displays the quadrature-axis component of voltage setpoint Uq.
Index: [0] = Unsmoothed
[1] = Smoothed with p0045
p1730[0...n] Isd controller integral component shutdown threshold / Isd_ctr I_compDeac
Access level: 4 Calculated: p0340 = 1,3,4 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
30 [%] 150 [%] 30 [%]
p1731[0...n] Isd controller combination current time component / Isd ctrl iCombi T1
Access level: 4 Calculated: p0340 = 1,3,4 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.00 [ms] 10000.00 [ms] 0.00 [ms]
r1732[0...1] CO: Direct-axis voltage setpoint / Direct U set
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2001 Dyn. index: -
Units group: 5_1 Unit selection: p0505 Func. diagram: 1630, 5714, 6714,
5718
Min Max Factory setting
- [Vrms] - [Vrms] - [Vrms]
r1733[0...1] CO: Quadrature-axis voltage setpoint / Quad U set
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2001 Dyn. index: -
Units group: 5_1 Unit selection: p0505 Func. diagram: 1630, 5714, 5718,
6714, 6719
Min Max Factory setting
- [Vrms] - [Vrms] - [Vrms]