Siemens SINAMICS G120D - p2652 BI: EPOS direct setpoint input;MDI direction selection negative; MDI dir_sel neg; p2653 BI: EPOS direct setpoint input;MDI setting-up selection; MDI setting­up sel; p2654 CI: EPOS direct setpoint input;MDI mode adaptation; MDI mode adapt

Siemens SINAMICS G120D
910 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of parameters
1-358
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
0 signal / 1 signal: Absolute positioning in the negative direction.
1 signal / 1 signal: Absolute positioning through the shortest distance.
Description: Sets the signal source for the negative direction selection in the operating mode "direct setpoint input/MDI".
Dependency: Refer to: p2576, p2648, p2649, p2650, p2651, p2653, p2654
Note: The following applies for "setting-up":
- the traversing direction can be entered using this binector input.
- if both directions (p2651, p2652) are selected, then the axis remains stationary (zero speed).
- if both directions (p2651, p2652) are de-selected, then the axis remains stationary (zero speed).
The following applies for "positioning":
Using binector inputs p2651 and p2652, when the modulo correction (BI: p2577 = 1 signal) is activated and for
absolute positioning (BI: p2648 = 1 signal), the traversing direction is specified as follows:
BI: p2651 / BI: p2652
0 signal / 0 signal: Absolute positioning through the shortest distance.
1 signal / 0 signal: Absolute positioning in the positive direction.
0 signal / 1 signal: Absolute positioning in the negative direction.
1 signal / 1 signal: Absolute positioning through the shortest distance.
Description: Sets the signal source for setting-up in the operating mode "direct setpoint input/MDI".
BI: p2653 = 1 signal
Setting-up selected.
BI: p2653 = 0 signal
Positioning selected.
Dependency: Refer to: p2651, p2652
Note: In the operating mode "direct setpoint input/MDI", it is possible to make a flying changeover between setting-up and
positioning.
For "setup" (BI: p2653 = 1 signal), the following applies:
A traversing direction must be selected via binector inputs p2651 and p2652.
Description: Sets the signal source to interconnect the MDI mode to the operating mode "direct setpoint input MDI" via PROFI-
BUS telegram 110.
CI: p2654 = 0
The binector inputs listed below are evaluated.
CI: p2654 > 0
p2652 BI: EPOS direct setpoint input/MDI direction selection negative / MDI dir_sel neg
CU250D-2_DP_F
CU250D-2_PN_F
Access level: 1 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 3620
Min Max Factory setting
- - 0
p2653 BI: EPOS direct setpoint input/MDI setting-up selection / MDI setting-up sel
CU250D-2_DP_F
CU250D-2_PN_F
Access level: 1 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 3620
Min Max Factory setting
- - 0
p2654 CI: EPOS direct setpoint input/MDI mode adaptation / MDI mode adapt
CU250D-2_DP_F
CU250D-2_PN_F
Access level: 1 Calculated: - Data type: U32 / Integer16
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 3620
Min Max Factory setting
- - 0