List of faults and alarms
Faults and alarms
3-811
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
A02056 Trace: Recording cycle too short
Reaction: NONE
Acknowledge: NONE
Cause: The selected recording cycle is shorter than the selected basic clock cycle 0 (p0110[0]).
Remedy: Increase the value for the trace cycle.
A02057 Trace: Time slice clock cycle invalid
Reaction: NONE
Acknowledge: NONE
Cause: The time slice clock cycle selected does not match any of the existing time slices.
Remedy: Enter an existing time slice clock cycle. The existing time slices can be read out via p7901.
See also: r7901 (Sampling times)
A02058 Trace: Time slice clock cycle for endless trace not valid
Reaction: NONE
Acknowledge: NONE
Cause: The selected time slice clock cycle cannot be used for the endless trace
Remedy: Enter the clock cycle of an existing time slice with a cycle time >= 2 ms for up to 4 recording channels or >= 4 ms
from 5 recording channels per trace.
The existing time slices can be read out via p7901.
See also: r7901 (Sampling times)
A02059 Trace: Time slice clock cycle for 2 x 8 recording channels not valid
Reaction: NONE
Acknowledge: NONE
Cause: The selected time slice clock cycle cannot be used for more than 4 recording channels.
Remedy: Enter the clock cycle of an existing time slice with a cycle time >= 4 ms or reduce the number of recording channels
to 4 per trace.
The existing time slices can be read out via p7901.
See also: r7901 (Sampling times)
A02060 Trace: Signal to be traced missing
Reaction: NONE
Acknowledge: NONE
Cause: - a signal to be traced was not specified.
- the specified signals are not valid.
Remedy: - specify the signal to be traced.
- check whether the relevant signal can be traced.
A02061 Trace: Invalid signal
Reaction: NONE
Acknowledge: NONE
Cause: - the specified signal does not exist.
- the specified signal can no longer be traced (recorded).
Remedy: - specify the signal to be traced.
- check whether the relevant signal can be traced.
A02062 Trace: Invalid trigger signal
Reaction: NONE
Acknowledge: NONE
Cause: - a trigger signal was not specified.
- the specified signal does not exist.
- the specified signal is not a fixed-point signal.
- the specified signal cannot be used as a trigger signal for the trace.
Remedy: Specify a valid trigger signal.