Description: Sets the signal source for the command "continue ramp-function generator/freeze ramp-function generator".
For the PROFIdrive profile, this command corresponds to control word 1 bit 5 (STW1.5).
BI: p1141 = 0 signal:
Freezes the ramp-function generator.
BI: p1141 = 1 signal:
Continue ramp-function generator.
Dependency: Refer to: r0054, p1140, p1142
Caution: When "master control from PC" is activated, this binector input is ineffective.
Notice: The ramp-function generator is, independent of the state of the signal source, active in the following cases:
- OFF1/OFF3.
- ramp-function generator output within the suppression bandwidth.
- ramp-function generator output below the minimum speed.
Description: Sets the signal source for the command "enable setpoint/inhibit setpoint".
For the PROFIdrive profile, this command corresponds to control word 1 bit 6 (STW1.6).
BI: p1142 = 0 signal
Inhibits the setpoint (the ramp-function generator input is set to zero).
BI: p1142 = 1 signal
Setpoint enable.
Dependency: Refer to: p1140, p1141
Caution: When "master control from PC" is activated, this binector input is ineffective.
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: When the function module "position control" (r0108.3 = 1) is activated, this binector input is interconnected as fol-
lows as standard:
BI: p1142 = 0 signal
p1141[0...n] BI: Continue ramp-function generator/freeze ramp-function generator / Continue RFG
CU250D-2_DP_F
CU250D-2_PN_F
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 2501
Min Max Factory setting
- - 1
p1142[0...n] BI: Enable setpoint/inhibit setpoint / Setpoint enable
CU240D-2_DP
CU240D-2_DP_F
CU240D-2_PN
CU240D-2_PN_F
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 2501
Min Max Factory setting
- - [0] 2090.6
[1] 1
[2] 2090.6
[3] 2090.6