Siemens SINAMICS G120D - p2591 BI: EPOS jogging incremental; Jog incr; p2593 CI: EPOS LU;revolution LU;mm; LU;rev LU;mm; p2594[0...2] CI: EPOS Maximum velocity externally limited; v_Max ext lim; p2595 BI: EPOS referencing start; Ref start

Siemens SINAMICS G120D
910 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of parameters
1-342
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description: Sets the signal source for jogging incremental.
Dependency: Refer to: p2585, p2586, p2587, p2588, p2589, p2590
Description: Sets the signal source for the reference of the internal length units LU to motor revolution for rotary encoders and to
mm for linear encoders.
Dependency: Refer to: p0404, r2524, p2594
Note: The signal value is used to convert the length unit to the speed or velocity setpoint.
Description: Sets the signal source for the externally limited maximum velocity.
Index: [0] = Setpoint limit absolute
[1] = Setpoint limiting positive
[2] = Setpoint limiting negative
Dependency: Refer to: r2524, p2571, p2593
Warning: In order that the externally limited velocity can be effective for the EPOS operating modes, connector input p2593
must be correctly interconnected.
Description: Sets the signal source to start the "search for reference" or "flying referencing".
BI: p2595 = 0/1 signal
Referencing is started.
BI: p2595 = 1/0 signal
Referencing is interrupted.
Dependency: Refer to: p2597, p2598, p2599, r2684
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p2591 BI: EPOS jogging incremental / Jog incr
CU250D-2_DP_F
CU250D-2_PN_F
Access level: 1 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 3610
Min Max Factory setting
- - 722.5
p2593 CI: EPOS LU/revolution LU/mm / LU/rev LU/mm
CU250D-2_DP_F
CU250D-2_PN_F
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 3630
Min Max Factory setting
- - 2524[0]
p2594[0...2] CI: EPOS Maximum velocity externally limited / v_Max ext lim
CU250D-2_DP_F
CU250D-2_PN_F
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: p2000 Dyn. index: -
Units group: - Unit selection: - Func. diagram: 3630
Min Max Factory setting
- - 0
p2595 BI: EPOS referencing start / Ref start
CU250D-2_DP_F
CU250D-2_PN_F
Access level: 1 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 3612, 3625, 3614
Min Max Factory setting
- - 0