List of parameters
Parameters
1-115
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Description: Sets the scaling characteristic for the analog inputs.
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the y coordinate (percentage) of the 2nd value pair of the characteristic.
Index: [0] = AI0 (X10.3)
[1] = AI1 (X10.4)
Note: The parameters for the characteristic do not have a limiting effect.
Description: Sets the response threshold for the wire breakage monitoring of the analog inputs.
The unit for the parameter value depends on the set analog input type.
Index: [0] = AI0 (X10.3)
[1] = AI1 (X10.4)
Dependency: For the following analog input type, the wire breakage monitoring is active:
p0756[0...1] = 1 (unipolar voltage input monitored (+2 V ... +10 V)), unit [V]
Refer to: p0756
Note: AI: Analog Input
When p0761 = 0, wire breakage monitoring is not carried out.
Description: Sets the delay time for the wire breakage monitoring of the analog inputs.
Index: [0] = AI0 (X10.3)
[1] = AI1 (X10.4)
Note: AI: Analog Input
p0760[0...1] CU analog inputs characteristic value y2 / CU AI char y2
CU240D-2_DP
CU240D-2_DP_F
CU240D-2_PN
CU240D-2_PN_F
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 9566, 9568, 9576
Min Max Factory setting
-1000.00 [%] 1000.00 [%] 100.00 [%]
p0761[0...1] CU analog inputs wire breakage monitoring response threshold / CU WireBrkThresh
CU240D-2_DP
CU240D-2_DP_F
CU240D-2_PN
CU240D-2_PN_F
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 9566, 9568
Min Max Factory setting
0.00 20.00 2.00
p0762[0...1] CU analog inputs wire breakage monitoring delay time / CU wire brk t_del
CU240D-2_DP
CU240D-2_DP_F
CU240D-2_PN
CU240D-2_PN_F
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 9566, 9568
Min Max Factory setting
0 [ms] 1000 [ms] 100 [ms]