List of parameters
Parameters
1-253
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
7: 19200 baud
8: 38400 baud
9: 57600 baud
10: 76800 baud
11: 93750 baud
12: 115200 baud
Note: COMM-IF: Commissioning interface
The parameter is not influenced by setting the factory setting.
Description: Sets the address for the commissioning interface (USS, RS232).
Note: The parameter is not influenced by setting the factory setting.
Description: Selects the PZD (actual values) to be sent via the commissioning interface USS.
The actual values are displayed on an intelligent operator panel (IOP).
Index: [0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
Description: Displays the receive errors at the commissioning interface (USS, RS232).
Index: [0] = Number of error-free telegrams
[1] = Number of rejected telegrams
[2] = Number of framing errors
[3] = Number of overrun errors
[4] = Number of parity errors
[5] = Number of starting character errors
[6] = Number of checksum errors
[7] = Number of length errors
Description: Sets the communication protocol for the field bus interface.
p2011 Comm IF address / Comm add
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 31 2
p2016[0...3] CI: Comm IF USS PZD send word / Comm USS send word
Access level: 3 Calculated: - Data type: U32 / Integer16
Can be changed: U, T Scaling: 4000H Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0
r2019[0...7] Comm IF error statistics / Comm err
Access level: 4 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
p2030 Field bus int protocol selection / Field bus protocol
CU240D-2_DP
CU240D-2_DP_F
CU250D-2_DP_F
Access level: 1 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 3 3