List of parameters
Parameters
1-231
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Dependency: In U/f characteristic operating mode only bit 7 is relevant.
For active motor model feedback (see p1784), the Lh adaptation is internally deactivated automatically.
Note: ASM: Induction motor
PEM: Permanent magnet synchronous motor
When selecting the compensation of the valve interlocking via Rs (bit 7), the compensation in the gating unit is de-
activated and is instead taken into account in the motor model.
In order that the correction values of the Rs, Lh and kT adaptation (selected using Bit 0 ... Bit 2) are correctly
accepted when changing over the drive data set, a dedicated motor number must be entered into p0826 for each
different motor.
Description: Sets the scaling for model fault feedback.
Note: Feeding back the measured model fault to the model states increases the control stability and makes the motor
model rugged against parameter errors.
When feedback is selected (p1784 > 0), Lh adaptation is not effective.
Description: Sets the proportional gain for the Lh adaptation of the motor model for an induction motor (ASM).
Description: Sets the integral time for the Lh adaptation of the motor model for an induction motor (ASM).
Description: Displays the corrective value for the Lh adaptation of the motor model for an induction motor (ASM).
Dependency: Refer to: p0826, p1780
Note: The adaptation result is reset if the magnetizing inductance of the induction motor is changed (p0360, r0382). This
also happens when changing over the data set if a different motor is not being used (p0826).
The display of the inactive data sets is only updated when changing over the data set.
p1784[0...n] Motor model feedback scaling / MotMod fdbk scal
Access level: 4 Calculated: p0340 = 1,3,4 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.0 [%] 1000.0 [%] 0.0 [%]
p1785[0...n] Motor model Lh adaptation Kp / MotMod Lh Kp
Access level: 4 Calculated: p0340 = 1,3,4 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.000 10.000 0.100
p1786[0...n] Motor model Lh adaptation integral time / MotMod Lh Tn
Access level: 4 Calculated: p0340 = 1,3,4 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
10 [ms] 10000 [ms] 100 [ms]
r1787[0...n] Motor model Lh adaptation corrective value / MotMod Lh corr
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- [mH] - [mH] - [mH]