List of parameters
Parameters
1-113
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Note: AI: Analog Input
Description: Displays the actual input voltage in V.
Index: [0] = AI0 (X10.3)
[1] = AI1 (X10.4)
Dependency: The type of analog input AIx is set using p0756.
Refer to: p0756
Note: AI: Analog Input
Description: Sets the smoothing time constant of the 1st-order low pass filter for the analog inputs.
Index: [0] = AI0 (X10.3)
[1] = AI1 (X10.4)
Note: AI: Analog Input
Description: Displays the currently referred input value of the analog inputs.
When interconnected, the signals are referred to the reference quantities p200x and p205x.
Index: [0] = AI0 (X10.3)
[1] = AI1 (X10.4)
Note: AI: Analog Input
Description: Sets the type of analog inputs.
p0756[0...1] = 0 corresponds to a voltage input (r0752, p0757, p0759 are displayed in V).
01 Analog input AI1 wire breakage Yes No -
08 Analog input AI0 no wire breakage Yes No -
09 Analog input AI1 no wire breakage Yes No -
r0752[0...1] CO: CO: CU analog inputs input voltage/current actual / CU AI U/I_inp act
CU240D-2_DP
CU240D-2_DP_F
CU240D-2_PN
CU240D-2_PN_F
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 9566, 9568, 9576
Min Max Factory setting
- - -
p0753[0...1] CU analog inputs smoothing time constant / CU AI T_smooth
CU240D-2_DP
CU240D-2_DP_F
CU240D-2_PN
CU240D-2_PN_F
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 9566, 9568, 9576
Min Max Factory setting
0.0 [ms] 1000.0 [ms] 0.0 [ms]
r0755[0...1] CO: CO: CU analog inputs actual value in percent / CU AI value in %
CU240D-2_DP
CU240D-2_DP_F
CU240D-2_PN
CU240D-2_PN_F
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dyn. index: -
Units group: - Unit selection: - Func. diagram: 9566, 9568, 9576
Min Max Factory setting
- [%] - [%] - [%]
p0756[0...1] CU analog inputs type / CU AI type
CU240D-2_DP
CU240D-2_DP_F
CU240D-2_PN
CU240D-2_PN_F
Access level: 2 Calculated: - Data type: Integer16
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 9566, 9568, 9576
Min Max Factory setting
0 8 0