Parameters
List of parameters
1-46
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Description: Assign a drive data set (= index) the corresponding encoder data set (EDS) for encoder 1.
The value corresponds to the number of the assigned encoder data set.
Example:
Encoder data set 0 should be assigned to encoder 1 in drive data set 2.
--> p0187[2] = 0
Note: A value of 99 means that no encoder has been assigned to this drive data set (not configured).
Description: Assign a drive data set (= index) the corresponding encoder data set (EDS) for encoder 2.
The value corresponds to the number of the assigned encoder data set.
Example:
Encoder data set 1 should be assigned to encoder 2 in drive data set 2.
--> p0188[2] = 1
Note: A value of 99 means that no encoder has been assigned to this drive data set (not configured).
Description: Displays the bootloader version.
Index 0:
Displays the bootloader version.
Index 1:
Displays the bootloader version 3 (for CU320-2 and CU310-2)
Value 0 means that boot loader 3 is not available.
Dependency: Refer to: r0018, r0198
Note: Example:
The value 1010100 should be interpreted as V01.01.01.00.
p0187[0...n] Encoder 1 encoder data set number / Enc 1 EDS number
Access level: 3 Calculated: - Data type: Unsigned8
Can be changed: C(4) Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 1580, 8570
Min Max Factory setting
0 0 0
p0188[0...n] Encoder 2 encoder data set number / Enc 2 EDS number
CU250D-2_DP_F
CU250D-2_PN_F
Access level: 3 Calculated: - Data type: Unsigned8
Can be changed: C(4) Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 1580, 8570
Min Max Factory setting
1 1 1
r0197[0...1] Bootloader version / Bootloader vers
Access level: 4 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -