List of parameters
Parameters
1-57
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
For induction motors that are connected in parallel, but which are not mechanically coupled with one another, then
the following applies:
- an individual motor must not be loaded beyond its stall point.
Notice: If p0306 is changed during quick commissioning (p0010 = 1), then the maximum current p0640 is appropriately pre-
assigned.
Note: Only operation with U/f characteristic makes sense if more than 10 identical motors are connected in parallel.
Description: Sets the rated motor power (rating plate).
Dependency: IECdrives (p0100 = 0): Units kW
NEMA drives (p0100 = 1): Units hp
NEMA drives (p0100 = 2): Unit kW
Refer to: p0100
Caution: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected. Infor-
mation in p0300 should be carefully observed when removing write protection.
Note: Once the Control Unit has booted for the first time or if the factory settings have been restored, the parameter is
pre-assigned to match the power unit.
Description: Sets the rated motor power factor (cos phi, rating plate).
For a parameter value of 0.000, the power factor is internally calculated and displayed in r0332.
Dependency: This parameter is only available for p0100 = 0, 2.
Refer to: p0100, p0309, r0332
Caution: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected. Infor-
mation in p0300 should be carefully observed when removing write protection.
Note: The parameter is not used for synchronous motors (p0300 = 2xx).
Once the Control Unit has booted for the first time or if the factory settings have been restored, the parameter is
pre-assigned to match the power unit.
Description: Sets the rated motor efficiency (rating plate).
For a parameter value of 0.0, the power factor is internally calculated and displayed in r0332.
Dependency: This parameter is only available for NEMA motors (p0100 = 1).
Refer to: p0100, p0308, r0332
Note: The parameter is not used for synchronous motors.
p0307[0...n] Rated motor power / Mot P_rated
Access level: 1 Calculated: - Data type: FloatingPoint32
Can be changed: C(1, 3) Scaling: - Dyn. index: MDS
Units group: 14_6 Unit selection: p0100 Func. diagram: -
Min Max Factory setting
0.00 [kW] 100000.00 [kW] 0.00 [kW]
p0308[0...n] Rated motor power factor / Mot cos_phi_rated
Access level: 1 Calculated: - Data type: FloatingPoint32
Can be changed: C(1, 3) Scaling: - Dyn. index: MDS
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.000 1.000 0.000
p0309[0...n] Rated motor efficiency / Mot eta_rated
Access level: 1 Calculated: - Data type: FloatingPoint32
Can be changed: C(1, 3) Scaling: - Dyn. index: MDS
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.0 [%] 99.9 [%] 0.0 [%]