Parameters
List of parameters
1-288
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Description: Sets the speed threshold value for the "speed setpoint - actual value deviation in tolerance t_off" signal/message
(BO: r2197.7).
Dependency: Refer to: p2164, p2166, r2197
Description: Sets the hysteresis speed (bandwidth) for the "speed setpoint - actual value deviation in tolerance t_off" signal/mes-
sage (BO: r2197.7).
Dependency: Refer to: p2163, p2166, r2197
Description: Sets the switch-off delay time for the "speed setpoint - actual value deviation in tolerance t_off" signal/message
(BO: r2197.7).
Dependency: Refer to: p2163, p2164, r2197
Description: Sets the switch-on delay for the "speed setpoint - actual value deviation in tolerance t_on" signal/message (BO:
r2199.4).
Description: Displays the smoothed actual speed for messages/signals.
Dependency: Refer to: p2153
p2163[0...n] Speed threshold 4 / n_thresh val 4
Access level: 3 Calculated: p0340 = 1,3,5 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: 3_1 Unit selection: p0505 Func. diagram: 8010
Min Max Factory setting
0.00 [rpm] 210000.00 [rpm] 90.00 [rpm]
p2164[0...n] Hysteresis speed 4 / n_hysteresis 4
Access level: 3 Calculated: p0340 = 1,3,5 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: 3_1 Unit selection: p0505 Func. diagram: 8010
Min Max Factory setting
0.00 [rpm] 200.00 [rpm] 2.00 [rpm]
p2166[0...n] Off delay n_act = n_set / t_del_off n_i=n_so
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 8010
Min Max Factory setting
0.0 [ms] 10000.0 [ms] 200.0 [ms]
p2167[0...n] Switch-on delay n_act = n_set / t_on n_act=n_set
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 8010
Min Max Factory setting
0.0 [ms] 10000.0 [ms] 200.0 [ms]
r2169 CO: Actual speed smoothed signals / n_act smth message
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2000 Dyn. index: -
Units group: 3_1 Unit selection: p0505 Func. diagram: 1750, 8010, 8012,
8013
Min Max Factory setting
- [rpm] - [rpm] - [rpm]