List of parameters
Parameters
1-311
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Description: Displays the error (system deviation) between the setpoint and actual value of the technology controller.
Dependency: Refer to: p2263
Description: Sets the time constant for the differentiation (D component) of the technology controller.
Note: p2274 = 0: Differentiation is disabled.
Description: Sets the proportional gain (P component) of the technology controller.
Note: p2280 = 0: The proportional gain is disabled.
Description: Sets the integral time (I component, integrating time constant) of the technology controller.
Notice: The following applies for p2251 = 0:
If the output of the technology controller lies within the range of a suppression (skip) bandwidth (p1091 ... p1094,
p1101) or below the minimum speed (p1080), the integral component of the controller is held so that the controller
temporarily works as a P controller. This is necessary in order to prevent the controller from behaving in an unstable
manner, as the ramp-function generator switches to the parameterized up and down ramps (p1120, p1121) at the
same time in order to avoid setpoint steps. This state can be exited or avoided by changing the controller setpoint or
by using the start speed (= minimum speed).
Note: When the controller output reaches the limit, the I component of the controller is held.
p2285 = 0:
The integral time is disabled and the I component of the controller is reset.
r2273 CO: Technology controller error / Tec_ctrl error
CU240D-2_DP
CU240D-2_DP_F
CU240D-2_PN
CU240D-2_PN_F
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dyn. index: -
Units group: 9_1 Unit selection: p0595 Func. diagram: 7958
Min Max Factory setting
- [%] - [%] - [%]
p2274 Technology controller differentiation time constant / Tec_ctrl D comp T
CU240D-2_DP
CU240D-2_DP_F
CU240D-2_PN
CU240D-2_PN_F
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7958
Min Max Factory setting
0.000 [s] 60.000 [s] 0.000 [s]
p2280 Technology controller proportional gain / Tec_ctrl Kp
CU240D-2_DP
CU240D-2_DP_F
CU240D-2_PN
CU240D-2_PN_F
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7958
Min Max Factory setting
0.000 1000.000 1.000
p2285 Technology controller integral time / Tec_ctrl Tn
CU240D-2_DP
CU240D-2_DP_F
CU240D-2_PN
CU240D-2_PN_F
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7958
Min Max Factory setting
0.000 [s] 10000.000 [s] 30.000 [s]