Siemens SINAMICS G120D - p1520[0...n] CO: Torque limit upper; M_max upper; p1521[0...n] CO: Torque limit lower; M_max lower; p1522[0...n] CI: Torque limit upper; M_max upper; p1523[0...n] CI: Torque limit lower; M_max lower

Siemens SINAMICS G120D
910 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of parameters
Parameters
1-209
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Description: Sets the fixed, upper torque limit.
Dependency: Refer to: p1521, p1522, p1523, r1538, r1539
Danger: Negative values when setting the upper torque limit (p1520 < 0) can result in the motor accelerating in an uncontrol-
lable fashion.
Notice: A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note: The torque limit is limited to 400% of the rated motor torque. When automatically calculating the motor/closed-loop
control parameters (p0340), the torque limit is set to match the current limit (p0640).
Description: Sets the fixed, lower torque limit.
Dependency: Refer to: p1520, p1522, p1523
Danger: Positive values when setting the lower torque limit (p1521 > 0) can result in the motor accelerating in an uncontrol-
lable fashion.
Notice: A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note: The torque limit is limited to 400% of the rated motor torque. When automatically calculating the motor/closed-loop
control parameters (p0340), the torque limit is set to match the current limit (p0640).
Description: Sets the signal source for the upper torque limit.
Dependency: Refer to: p1520, p1521, p1523
Danger: Negative values resulting from the signal source and scaling can cause the motor to accelerate in an uncontrolled
manner.
Description: Sets the signal source for the lower torque limit.
Dependency: Refer to: p1520, p1521, p1522
p1520[0...n] CO: Torque limit upper / M_max upper
Access level: 2 Calculated: p0340 = 1,3,5 Data type: FloatingPoint32
Can be changed: U, T Scaling: p2003 Dyn. index: DDS, p0180
Units group: 7_1 Unit selection: p0505 Func. diagram: 1700, 6630
Min Max Factory setting
-1000000.00 [Nm] 20000000.00 [Nm] 0.00 [Nm]
p1521[0...n] CO: Torque limit lower / M_max lower
Access level: 2 Calculated: p0340 = 1,3,5 Data type: FloatingPoint32
Can be changed: U, T Scaling: p2003 Dyn. index: DDS, p0180
Units group: 7_1 Unit selection: p0505 Func. diagram: 1700, 6630
Min Max Factory setting
-20000000.00 [Nm] 1000000.00 [Nm] 0.00 [Nm]
p1522[0...n] CI: Torque limit upper / M_max upper
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: p2003 Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 6630
Min Max Factory setting
- - 1520[0]
p1523[0...n] CI: Torque limit lower / M_max lower
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: p2003 Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 1700, 6630
Min Max Factory setting
- - 1521[0]