List of parameters
Parameters
1-437
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Dependency: Refer to: F01659
Note: It is not possible to change Safety Integrated parameters until the Safety Integrated password has been entered.
Description: Enters a new Safety Integrated password.
Dependency: A change made to the Safety Integrated password must be acknowledged in the following parameter:
Refer to: p9763
Description: Acknowledges the new Safety Integrated password.
Dependency: Refer to: p9762
Note: The new password entered into p9762 must be re-entered in order to acknowledge.
p9762 = p9763 = 0 is automatically set after the new Safety Integrated password has been successfully acknowl-
edged.
Description: Displays the time remaining until the next dynamization and testing of the safety motion monitoring functions inte-
grated in the drives.
The signal source to initiate the forced checking procedure is parameterized in p9705.
Dependency: Refer to: p9705
Refer to: C01798
Description: Displays the received PROFIsafe telegram on processor 1.
Index: [0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
[5] = PZD 6
p9762 SI password new / SI password new
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: C(95) Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 2800
Min Max Factory setting
0000 hex FFFF FFFF hex 0000 hex
p9763 SI password acknowledgement / SI ackn password
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: C(95) Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 2800
Min Max Factory setting
0000 hex FFFF FFFF hex 0000 hex
r9765 SI Motion forced checking procedure remaining time (processor 1) /
SI Mtn dyn rem P1
CU240D-2_DP_F
CU240D-2_PN_F
CU250D-2_DP_F
CU250D-2_PN_F
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- [h] - [h] - [h]
r9768[0...7] SI PROFIsafe receive control words (processor 1) / SI Ps PZD recv P1
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -

Table of Contents