Parameters
List of parameters
1-80
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Description: Sets the minimum delay time between two data transfers of the absolute value for an SSI encoder.
Notice: This parameter is automatically pre-set for encoders from the encoder list (p0400). When selecting a catalog
encoder, this parameter cannot be changed (write protection). Information in p0400 should be carefully observed
when removing write protection.
Description: Sets the configuration for an SSI encoder.
Caution: This parameter is automatically pre-set for encoders from the encoder list (p0400). When selecting a catalog
encoder, this parameter cannot be changed (write protection). Information in p0400 should be carefully observed
when removing write protection.
Note: Re bit 06:
The quiescent signal level of the data line corresponds to the inverted, set level.
Description: Sets the configuration of the Sensor Module.
Notice: A bit-wise configuration is only possible if the corresponding property is also present in r0458.
Note: Re bit 20 (speed calculation mode):
- if bit = 1, the speed is calculated via incremental difference without extrapolation.
- if bit = 0, the speed is calculated via edge time measurement with extrapolation. p0453 is effective in this mode.
Re bit 21 (zero mark tolerance):
- if bit = 1, a one-off zero mark distance error is tolerated. In the event of a defect, the fault F3x100/F3x101 does not
appear, but alarm A3x400/A3x401 does.
p0428[0...n] Encoder SSI monoflop time / Enc SSI t_monoflop
CU250D-2_DP_F
CU250D-2_PN_F
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: C(4) Scaling: - Dyn. index: EDS, p0140
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 [µs] 65535 [µs] 30 [µs]
p0429[0...n] Encoder SSI configuration / Enc SSI config
CU250D-2_DP_F
CU250D-2_PN_F
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: C(4) Scaling: - Dyn. index: EDS, p0140
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Transfer code Binary code Gray code -
02 Transfer absolute value twice Yes No -
06 Data line during the monoflop time High level Low level -
p0430[0...n] Sensor Module configuration / SM config
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: C(4) Scaling: - Dyn. index: EDS, p0140
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0000 0000 0000 0000 0000 0000
0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
20 Speed calculation mode (only SMC30) Incremental diff Flank time meas -
21 Zero mark tolerance Yes No -
25 Switch off encoder voltage supply during
parking
Yes No -
27 Extrapolate position values Yes No -