Parameters
List of parameters
1-84
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Description: Sets the number of bits before the absolute value in the SSI protocol.
Caution: This parameter is automatically pre-set for encoders from the encoder list (p0400). When selecting a catalog
encoder, this parameter cannot be changed (write protection). Information in p0400 should be carefully observed
when removing write protection.
Note: For example, error bit, alarm bit or parity bit can be positioned at these bits.
Description: Sets the number of bits for the absolute value in the SSI protocol.
Caution: This parameter is automatically pre-set for encoders from the encoder list (p0400). When selecting a catalog
encoder, this parameter cannot be changed (write protection). Information in p0400 should be carefully observed
when removing write protection.
Description: Sets the number of bits after the absolute value in the SSI protocol.
Caution: This parameter is automatically pre-set for encoders from the encoder list (p0400). When selecting a catalog
encoder, this parameter cannot be changed (write protection). Information in p0400 should be carefully observed
when removing write protection.
Note: For example, error bit, alarm bit or parity bit can be positioned at these bits.
Description: Sets the number of filler bits for double absolute value transfer in the SSI protocol.
Dependency: Refer to: p0429
Caution: This parameter is automatically pre-set for encoders from the encoder list (p0400). When selecting a catalog
encoder, this parameter cannot be changed (write protection). Information in p0400 should be carefully observed
when removing write protection.
Note: This parameter is only of significance for p0429.2 = 1.
p0446[0...n] Encoder SSI number of bits before the absolute value / Enc SSI bit before
CU250D-2_DP_F
CU250D-2_PN_F
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: C(4) Scaling: - Dyn. index: EDS, p0140
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 65535 0
p0447[0...n] Encoder SSI number of bits absolute value / Enc SSI bit val
CU250D-2_DP_F
CU250D-2_PN_F
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: C(4) Scaling: - Dyn. index: EDS, p0140
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 65535 25
p0448[0...n] Encoder SSI number of bits after the absolute value / Enc SSI bit after
CU250D-2_DP_F
CU250D-2_PN_F
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: C(4) Scaling: - Dyn. index: EDS, p0140
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 65535 0
p0449[0...n] Encoder SSI number of bits filler bits / Enc SSI fill bits
CU250D-2_DP_F
CU250D-2_PN_F
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: C(4) Scaling: - Dyn. index: EDS, p0140
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 65535 1