Parameters
List of parameters
1-264
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Description: Sets the send and receive telegram.
Contrary to p0922, a telegram can be selected using p2079 and subsequently expanded.
Value: 7: Standard telegram 7, PZD-2/2
9: Standard telegram 9, PZD-10/5
110: SIEMENS telegram 110, PZD-12/7
111: SIEMENS telegram 111, PZD-12/12
999: Free telegram configuration with BICO
Dependency: Refer to: p0922
Note: For p0922 < 999 the following applies:
p2079 has the same value and is inhibited. All of the interconnections and extensions contained in the telegram are
inhibited.
For p0922 = 999 the following applies:
p2079 can be freely set. If p2079 is also set to 999, then all of the interconnections can be set.
For p0922 = 999 and p2079 < 999 the following applies:
The interconnections contained in the telegram are inhibited. However, the telegram can be extended.
Description: Selects bits to be sent to the PROFIdrive controller.
The individual bits are combined to form status word 1.
Index: [0] = Bit 0
[1] = Bit 1
[2] = Bit 2
[3] = Bit 3
[4] = Bit 4
[5] = Bit 5
[6] = Bit 6
p2079 PROFIdrive PZD telegram selection extended / PZD telegr ext
CU250D-2_DP_F
CU250D-2_PN_F
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
7 999 999
p2080[0...15] BI: Binector-connector converter status word 1 / Bin/con ZSW1
CU240D-2_DP
CU240D-2_DP_F
CU240D-2_PN
CU240D-2_PN_F
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 2472
Min Max Factory setting
- - [0] 899.0
[1] 899.1
[2] 899.2
[3] 2139.3
[4] 899.4
[5] 899.5
[6] 899.6
[7] 2139.7
[8] 2197.7
[9] 899.9
[10] 2199.1
[11] 1407.7
[12] 899.12
[13] 2135.14
[14] 2197.3
[15] 2135.15