List of parameters
Parameters
1-529
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Description: Setting parameter for the run-time group of instance DFR 2 within the run-time group set in p20332.
Note: The function blocks with a lower run sequence value are calculated before function blocks with a higher run
sequence value.
Description: Sets the signal source for the input pulse I of instance PDE 2 of the closing delay device.
Description: Setting parameter for pulse delay time T in milliseconds of instance PDE 2 of the closing delay device.
Description: Display parameter for output pulse Q of instance PDE 2 of the closing delay device.
Description: Setting parameter for the run-time group in which instance PDE 2 of the closing delay device is to be called.
Value: 5: Run-time group 5
6: Run-time group 6
9999: Do not calculate
p20333 DFR 2 run sequence / DFR 2 RunSeq
CU240D-2_DP
CU240D-2_DP_F
CU240D-2_PN
CU240D-2_PN_F
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7240
Min Max Factory setting
0 32000 870
p20334 BI: PDE 2 input pulse I / PDE 2 inp_pulse I
CU240D-2_DP
CU240D-2_DP_F
CU240D-2_PN
CU240D-2_PN_F
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7232
Min Max Factory setting
- - 0
p20335 PDE 2 pulse delay time in ms / PDE 2 t_del ms
CU240D-2_DP
CU240D-2_DP_F
CU240D-2_PN
CU240D-2_PN_F
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7232
Min Max Factory setting
0.00 5400000.00 0.00
r20336 BO: PDE 2 output Q / PDE 2 output Q
CU240D-2_DP
CU240D-2_DP_F
CU240D-2_PN
CU240D-2_PN_F
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7232
Min Max Factory setting
- - -
p20337 PDE 2 run-time group / PDE 2 RTG
CU240D-2_DP
CU240D-2_DP_F
CU240D-2_PN
CU240D-2_PN_F
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7232
Min Max Factory setting
5 9999 9999