List of parameters
Parameters
1-299
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Description: Sets the value for fixed value 7 of the technology controller.
Dependency: Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice: A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Description: Sets the value for fixed value 8 of the technology controller.
Dependency: Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice: A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Description: Sets the value for fixed value 9 of the technology controller.
Dependency: Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice: A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Description: Sets the value for fixed value 10 of the technology controller.
Dependency: Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice: A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
p2207[0...n] CO: Technology controller fixed value 7 / Tec_ctr fix val 7
CU240D-2_DP
CU240D-2_DP_F
CU240D-2_PN
CU240D-2_PN_F
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: DDS, p0180
Units group: 9_1 Unit selection: p0595 Func. diagram: 7950
Min Max Factory setting
-200.00 [%] 200.00 [%] 70.00 [%]
p2208[0...n] CO: Technology controller fixed value 8 / Tec_ctr fix val 8
CU240D-2_DP
CU240D-2_DP_F
CU240D-2_PN
CU240D-2_PN_F
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: DDS, p0180
Units group: 9_1 Unit selection: p0595 Func. diagram: 7950
Min Max Factory setting
-200.00 [%] 200.00 [%] 80.00 [%]
p2209[0...n] CO: Technology controller fixed value 9 / Tec_ctr fix val 9
CU240D-2_DP
CU240D-2_DP_F
CU240D-2_PN
CU240D-2_PN_F
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: DDS, p0180
Units group: 9_1 Unit selection: p0595 Func. diagram: 7950
Min Max Factory setting
-200.00 [%] 200.00 [%] 90.00 [%]
p2210[0...n] CO: Technology controller fixed value 10 / Tec_ctr fix val 10
CU240D-2_DP
CU240D-2_DP_F
CU240D-2_PN
CU240D-2_PN_F
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: DDS, p0180
Units group: 9_1 Unit selection: p0595 Func. diagram: 7950
Min Max Factory setting
-200.00 [%] 200.00 [%] 100.00 [%]