Siemens SINAMICS G120D - p1740[0...n] Gain resonance damping for encoderless closed-loop control; Gain res_damp; p1744[0...n] Motor model speed threshold stall detection; MotMod n_thr stall; p1745[0...n] Motor model error threshold stall detection; MotMod ThreshStall; r1746 Motor model error signal stall detection; MotMod sig stall

Siemens SINAMICS G120D
910 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of parameters
Parameters
1-223
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Description: Defines the gain of the controller for resonance damping for operation with sensorless vector control in the range
that current is injected.
Description: Sets the speed threshold value to detect a stalled motor.
If the adaptation controller output exceeds the parameterized speed difference, then bit 11 in status word p1408 is
set.
Dependency: If a stalled drive is detected (p1408.11 set), fault 7902 is output after the delay time in p2178.
Refer to: p2178
Note: Speed monitoring is only effective in operation with a speed encoder (refer to p1300).
Stalling is also identified if steps/jumps occur in the speed signal, which exceed the value in p0492.
Description: Sets the fault threshold in order to detect a motor that has stalled.
If the error signal (r1746) exceeds the parameterized error threshold, then status signal r1408.12 is set to 1.
Dependency: If a stalled drive is detected (r1408.12 = 1), fault F07902 is output after the delay time set in p2178.
Refer to: p2178
Note: Monitoring is only effective in the low-speed range (below p1755 * (100% - p1756)).
Description: Signal to initiate stall detection
Note: The signal is not calculated while magnetizing and only in the low speed range (below p1755 * (100 % - p1756)).
p1740[0...n] Gain resonance damping for encoderless closed-loop control / Gain res_damp
Access level: 3 Calculated: p0340 = 1,3,4 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.000 10.000 0.025
p1744[0...n] Motor model speed threshold stall detection / MotMod n_thr stall
Access level: 4 Calculated: p0340 = 1,3 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: 3_1 Unit selection: p0505 Func. diagram: -
Min Max Factory setting
0.00 [rpm] 210000.00 [rpm] 100.00 [rpm]
p1745[0...n] Motor model error threshold stall detection / MotMod ThreshStall
Access level: 3 Calculated: p0340 = 1,3 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.0 [%] 1000.0 [%] 5.0 [%]
r1746 Motor model error signal stall detection / MotMod sig stall
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- [%] - [%] - [%]