SINAMICS G120D List Manual (LH14), 01/2013
Description: Sets the absolute current threshold for the messages.
"I_act >= I_threshold p2170" (BO: r2197.8)
"I_act < I_threshold p2170" (BO: r2198.8)
Dependency: Refer to: p2171
Description: Sets the delay time for the comparison of the current actual value (r0068) with the current threshold value (p2170).
Dependency: Refer to: p2170
Description: Sets the DC link voltage threshold value for the following messages:
"Vdc_act <= Vdc_threshold p2172" (BO: r2197.9)
"Vdc_act > Vdc_threshold p2172" (BO: r2197.10)
Dependency: Refer to: p2173
Description: Sets the delay time for the comparison of the DC link voltage r0070 with the threshold value p2172.
Dependency: Refer to: p2172
Description: Sets the torque threshold value for the messages:
"Torque setpoint < torque threshold value 1 and n_set reached" (BO: r2198.9)
"Torque setpoint < torque threshold value 1" (BO: r2198.10)
"Torque setpoint > torque threshold value 1" (BO: r2198.13)
p2170[0...n] Current threshold value / I_thres
Access level: 3 Calculated: p0340 = 1,3,5 Data type: FloatingPoint32
Can be changed: U, T Scaling: p2002 Dyn. index: DDS, p0180
Units group: 6_2 Unit selection: p0505 Func. diagram: -
Min Max Factory setting
0.00 [Arms] 10000.00 [Arms] 0.00 [Arms]
p2171[0...n] Current threshold value reached delay time / t_del I_thresh rch
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 [ms] 10000 [ms] 10 [ms]
p2172[0...n] DC link voltage threshold value / Vdc thresh val
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: p2001 Dyn. index: DDS, p0180
Units group: 5_2 Unit selection: p0505 Func. diagram: -
Min Max Factory setting
0 [V] 2000 [V] 800 [V]
p2173[0...n] DC link voltage comparison delay time / t_del Vdc
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 [ms] 10000 [ms] 10 [ms]
p2174[0...n] Torque threshold value 1 / M_thresh val 1
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: 7_1 Unit selection: p0505 Func. diagram: 8012
Min Max Factory setting
0.00 [Nm] 20000000.00 [Nm] 5.13 [Nm]