Parameters
List of parameters
1-434
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Description: Re index 0:
Displays the message value that resulted in the STOP F on the drive.
Value = 0:
Processor 1 signaled a STOP F.
Value = 1 ... 999:
Number of the incorrect date in the crosswise data comparison between the monitoring channels.
Value >= 1000:
Additional diagnostic values of the drive.
Re index 1:
Displays the value from processor 1 that resulted in the STOP F.
Re index 2:
Displays the value from processor 2 that resulted in the STOP F.
Index: [0] = Message value for CDC
[1] = Processor 1 CDC actual value
[2] = Processor 2 CDC actual value
Dependency: Refer to: C01711
Note: The significance of the individual message values is described in message C01711.
CDC: Crosswise Data Comparison
Re Index 1, 2:
When Safety message C01711 with message value >= 1000 occurs, these indices are not supplied with values.
Description: Displays the checksum over the checked Safety Integrated parameters of the motion monitoring functions (actual
checksum).
Index: [0] = Checksum over SI parameters for motion monitoring
[1] = Checksum over SI parameters for actual values
[2] = Checksum over SI parameters for hardware
Dependency: Refer to: p9729
Refer to: F01680
Description: Sets the checksum using the checksum-tested Safety Integrated parameters for motion monitoring functions (refer-
ence checksum).
r9725[0...2] SI Motion diagnostics STOP F / SI Mtn Diag STOP F
CU240D-2_DP_F
CU240D-2_PN_F
CU250D-2_DP_F
CU250D-2_PN_F
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
r9728[0...2] SI Motion actual checksum SI parameters (processor 1) / SI Mtn act CRC P1
CU240D-2_DP_F
CU240D-2_PN_F
CU250D-2_DP_F
CU250D-2_PN_F
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
p9729[0...2] SI Motion setpoint checksum SI parameters (processor 1) / SI Mtn setp CRC P1
CU240D-2_DP_F
CU240D-2_PN_F
CU250D-2_DP_F
CU250D-2_PN_F
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: C(95) Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0000 hex FFFF FFFF hex 0000 hex