Siemens SINAMICS G120D - p0341[0...n] Motor moment of inertia; Mot M_mom of inert; p0342[0...n] Ratio between the total and motor moment of inertia; Mot MomInert Ratio; r0343[0...n] Rated motor current identified; Mot I_rated ident; p0344[0...n] Motor weight (for the thermal motor model); Mot weight th mod

Siemens SINAMICS G120D
910 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of parameters
Parameters
1-65
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
p0340 = 4 only calculates the controller parameters.
p0340 = 5 only calculates the controller limits.
When quick commissioning is exited using p3900 > 0, p0340 is automatically set to 1.
At the end of the calculations, p0340 is automatically set to 0.
Description: Sets the motor moment of inertia (without load).
Dependency: IEC drives (p0100 = 0): unit kg m^2
NEMA drives (p0100 = 1): unit lb ft^2
The parameter value is included, together with p0342, in the rated starting time of the motor.
Refer to: p0342, r0345
Caution: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected. Infor-
mation in p0300 should be carefully observed when removing write protection.
Note: The product of p0341 * p0342 is used when the speed controller (p0340 = 4) is calculated automatically.
Description: Sets the ratio between the total moment of inertia/mass (load + motor) and the intrinsic motor moment of iner-
tia/mass (no load).
Dependency: This means that together with p0341, the rated starting (accelerating time) of the motor is calculated for a vector
drive.
Refer to: p0341, r0345
Note: The product of p0341 * p0342 is used when the speed controller (p0340 = 4) is calculated automatically.
Description: Displays the identified rated motor current.
Description: Sets the motor weight.
Dependency: IEC drives (p0100 = 0): unit kg
NEMA drives (p0100 = 1): unit lb
p0341[0...n] Motor moment of inertia / Mot M_mom of inert
Access level: 3 Calculated: p0340 = 1 Data type: FloatingPoint32
Can be changed: C(3), U, T Scaling: - Dyn. index: MDS
Units group: 25_1 Unit selection: p0100 Func. diagram: 1700, 5042, 5210,
6030, 6031
Min Max Factory setting
0.000000 [kgm²] 100000.000000 [kgm²] 0.000000 [kgm²]
p0342[0...n] Ratio between the total and motor moment of inertia / Mot MomInert Ratio
Access level: 3 Calculated: p0340 = 1 Data type: FloatingPoint32
Can be changed: C(3), U, T Scaling: - Dyn. index: MDS
Units group: - Unit selection: - Func. diagram: 1700, 5042, 5210,
6030, 6031
Min Max Factory setting
1.000 10000.000 1.000
r0343[0...n] Rated motor current identified / Mot I_rated ident
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: MDS
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.00 [Arms] 10000.00 [Arms] - [Arms]
p0344[0...n] Motor weight (for the thermal motor model) / Mot weight th mod
Access level: 3 Calculated: p0340 = 1 Data type: FloatingPoint32
Can be changed: C(3), T Scaling: - Dyn. index: MDS
Units group: 27_1 Unit selection: p0100 Func. diagram: -
Min Max Factory setting
0.0 [kg] 50000.0 [kg] 0.0 [kg]