Fig. 2-11 2251 – Analog inputs (AI 0 ... AI 1)
- 2251 -
Function diagram
87654321
fp_2251_97_04.vsd
Input/Output Terminals
G120D CU240D-2
12.12.2012 V4.6
Analog inputs 0 ... 1 (AI 0 ... AI 1)
<2>
-10 V +10 V
X10.3
(X10.4)
[%]
xy
A
D
+
-
<1>
<1>
x
1
y
2
x
2
y
1
y
x
[%]
y
x
2
x
1
<2>
<3>
1
0
Hardware smoothing
100 μs
Scaling
Differential Input!
For an input signal referred to ground, terminal X10.7 must be connected to reference potential M.
Caution:
The maximum voltage difference between analog input terminals AI+, AI-, and the ground must not exceed 35 V.
Possible settings p0756[0] and p0756[1]:
= 0: Unipolar voltage input (0 V ... +10 V)
= 8: No sensor connected
r0752
CU AI U/I_inp act
X10.7
(X10.7)
<3>
Sampling time of the AI: 4 ms
r0755
CU AI value in % [%]
[0..1]
Values in brackets --> AI 1
Type switching
Analog input
AI 0/1
CU AI type
0 ... 8
p0756[0..1] (0)
CU AI sim_mode
0 ... 1
p0797[0..1] (0)
CU AI sim setp
-50.000 ... 2000.000
p0798[0..1] (0.000)
CU AI char y1
-1000.00 ... 1000.00 [%]
p0758[0..1] (0.00)
CU AI char y2
-1000.00 ... 1000.00 [%]
p0760[0..1] (100.00)
CU AI char x1
-50.000 ... 160.000
p0757[0..1] (0.000)
CU AI char x2
-50.000 ... 160.000
p0759[0..1] (10.000)
CU AI T_smooth
0.0 ... 1000.0 [ms]
p0753[0..1] (0.0)
Reference
quantities
p2000 r2004
100 %