If value = 255:
No terminal assigned, safety function always inactive.
F-DI: Failsafe Digital Input
STO: Safe Torque Off
Description: Sets the fail-safe digital input (F-DI) for the "SS1" function.
Value: 0: Statically active
1: F-DI 0
2: F-DI 1
3: F-DI 2
255: Statically inact
Dependency: Refer to: p10023
Note: If value = 0:
No terminal assigned, safety function always active.
If value = 255:
No terminal assigned, safety function always inactive.
F-DI: Failsafe Digital Input
SS1: Safe Stop 1
Description: Sets the fail-safe digital input (F-DI) for the "SLS" function.
Value: 0: Statically active
1: F-DI 0
2: F-DI 1
3: F-DI 2
255: Statically inact
Dependency: Refer to: p10026
Note: If value = 0:
No terminal assigned, safety function always active.
If value = 255:
No terminal assigned, safety function always inactive.
F-DI: Failsafe Digital Input
SLS: Safely-Limited Speed
p10123 SI SS1 input terminal (processor 2) / SI SS1 F-DI P2
CU240D-2_DP_F
CU240D-2_PN_F
CU250D-2_DP_F
CU250D-2_PN_F
Access level: 3 Calculated: - Data type: Integer16
Can be changed: C(95) Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 255 0
p10126 SI SLS input terminal (processor 2) / SI SLS F-DI P2
CU240D-2_DP_F
CU240D-2_PN_F
CU250D-2_DP_F
CU250D-2_PN_F
Access level: 3 Calculated: - Data type: Integer16
Can be changed: C(95) Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 255 0