Siemens SINAMICS G120D - p0854[0...n] BI: Control by PLC;no control by PLC; Master ctrl by PLC; p0855[0...n] BI: Unconditionally open holding brake; Uncond open brake

Siemens SINAMICS G120D
910 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of parameters
1-130
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
BI: p0854 = 0 signal
No control by PLC
BI: p0854 = 1 signal
Master ctrl by PLC.
Caution: When "master control from PC" is activated, this binector input is ineffective.
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: This bit is used to initiate a response for the drives when the control fails (F07220). If there is no control available,
then binector input p0854 should be set to 1.
If a control is available, then STW1.10 must be set to 1 (PZD1) so that the received data is updated. This applies
regardless of the setting in p0854 and even in the case of free telegram configuration (p0922 = 999).
Description: Sets the signal source for the command "control by PLC/no control by PLC".
For the PROFIdrive profile, this command corresponds to control word 1 bit 10 (STW1.10).
BI: p0854 = 0 signal
No control by PLC
BI: p0854 = 1 signal
Master ctrl by PLC.
Caution: When "master control from PC" is activated, this binector input is ineffective.
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: This bit is used to initiate a response for the drives when the control fails (F07220). If there is no control available,
then binector input p0854 should be set to 1.
If a control is available, then STW1.10 must be set to 1 (PZD1) so that the received data is updated. This applies
regardless of the setting in p0854 and even in the case of free telegram configuration (p0922 = 999).
Description: Sets the signal source for the command "unconditionally open holding brake".
Dependency: Refer to: p0858
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: The signal via BI: p0858 (unconditionally close holding brake) has a higher priority than via BI: p0855 (uncondition-
ally open holding brake).
p0854[0...n] BI: Control by PLC/no control by PLC / Master ctrl by PLC
CU250D-2_DP_F
CU250D-2_PN_F
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 2501, 8720, 8820,
8920
Min Max Factory setting
- - 1
p0855[0...n] BI: Unconditionally open holding brake / Uncond open brake
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 2501, 2701
Min Max Factory setting
- - 0