Parameters
List of parameters
1-54
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Description: Sets the alarm threshold for power unit overtemperatures. The value is set as a difference to the tripping (shut-
down) temperature.
Drive:
If this threshold is exceeded, an overload alarm is generated and the system responds as parameterized in p0290.
Infeed:
When the threshold value is exceeded, only an overload alarm is output.
Index: [0] = Heat sink temperature
[1] = Power semiconductor (chip) temperature
Dependency: Refer to: r0037, p0290
Refer to: A05000
Description: Sets the alarm threshold for the I2t power unit overload.
If this threshold is exceeded, an overload alarm is generated and the system responds as parameterized in p0290.
Dependency: Refer to: r0036, p0290
Refer to: A07805
Note: The I2t fault threshold is 100 %. If this value is exceeded, fault F30005 is output.
Description: Sets the fan run-on time after the pulses for the power unit have been canceled.
Note: - Under certain circumstances, the fan can continue to run for longer than was set (e.g. as a result of the exces-
sively high heat sink temperature).
- For values less than 1 s, a 1 s run on time for the fan is active.
Description: Threshold to detect a DC link undervoltage.
If the DC link voltage falls below this threshold, the drive unit is tripped due to a DC link undervoltage condition.
Dependency: Refer to: F30003
p0292[0...1] Power unit temperature alarm threshold / PU T_alrm thresh
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 [°C] 25 [°C] [0] 5 [°C]
[1] 15 [°C]
p0294 Power unit alarm with I2t overload / PU I2t alrm thresh
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 8014
Min Max Factory setting
10.0 [%] 100.0 [%] 95.0 [%]
p0295 Fan run-on time / Fan run-on time
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 [s] 600 [s] 0 [s]
r0296 DC link voltage undervoltage threshold / Vdc U_lower_thresh
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- [V] - [V] - [V]