Value: 0: No protocol
3: PROFIBUS
Notice: For p0014 = 1, the following applies:
After the value has been modified, no further parameter modifications can be made and the status is shown in
r3996. Modifications can be made again when r3996 = 0.
Note: Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
Description: Sets the communication protocol for the field bus interface.
Value: 0: No protocol
7: PROFINET
10: Ethernet/IP
Notice: For p0014 = 1, the following applies:
After the value has been modified, no further parameter modifications can be made and the status is shown in
r3996. Modifications can be made again when r3996 = 0.
Note: Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
Description: Displays the effective control word 1 (STW1) of the drive for the master control.
Notice: The master control only influences control word 1 and speed setpoint 1. Other control words/setpoints can be trans-
ferred from another automation device.
Note: OC: Operating condition
p2030 Field bus int protocol selection / Field bus protocol
CU240D-2_PN
CU240D-2_PN_F
CU250D-2_PN_F
Access level: 1 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 10 7
r2032 Master control control word effective / PcCtrl STW eff
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 ON/OFF1 Yes No -
01 OC / OFF2 Yes No -
02 OC / OFF3 Yes No -
03 Operation enable Yes No -
04 Ramp-function generator enable Yes No -
05 Start ramp-function generator Yes No -
06 Speed setpoint enable Yes No -
07 Acknowledge fault Yes No -
08 Jog bit 0 Yes No 3030
09 Jog bit 1 Yes No 3030
10 Master ctrl by PLC Yes No -