Description: Determines the width of the dead zone at the analog input.
Analog input type unipolar (e.g. 0 ... +10 V):
The dead zone starts with the characteristic value x1/y1 (p0757/p0758).
Analog input type bipolar (e.g. -10 V ... +10 V):
The dead zone is located at the symmetrical center between characteristic value x1/y1 (p0757/p0758) and x2/y2
(p0759/p0760). The set value doubles the dead zone.
Index: [0] = AI0 (X10.3)
[1] = AI1 (X10.4)
Note: AI: Analog Input
T: Terminal
Description: Sets the simulation mode for digital inputs.
Dependency: The setpoint for the input signals is specified using p0796.
Refer to: p0796
Note: This parameter is not saved when data is backed up (p0971).
AI: Analog Input
DI: Digital Input
Description: Sets the simulation mode for digital inputs.
p0764[0...1] CU analog inputs dead zone / CU AI dead zone
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 2251
Min Max Factory setting
0.000 [V] 20.000 [V] 0.000 [V]
p0795 CU digital inputs simulation mode / CU DI simulation
CU240D-2_DP
CU240D-2_DP_F
CU240D-2_PN
CU240D-2_PN_F
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 1510, 2020, 2030,
2031, 2100, 2120, 2130, 2131, 2132,
2133
Min Max Factory setting
- - 0000 0000 0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI0 (X07.1) Simulation Terminal eval -
01 DI1 (X07.2) Simulation Terminal eval -
02 DI2 (X08.1) Simulation Terminal eval -
03 DI3 (X08.2) Simulation Terminal eval -
04 DI4 (X09.1) Simulation Terminal eval -
05 DI5 (X09.2) Simulation Terminal eval -
11 DI11 (X10.3, 7) AI0 Simulation Terminal eval -
12 DI12 (X10.4, 7) AI1 Simulation Terminal eval -
p0795 CU digital inputs simulation mode / CU DI simulation
CU250D-2_DP_F
CU250D-2_PN_F
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 1510, 2020, 2030,
2031, 2100, 2120, 2130, 2131, 2132,
2133
Min Max Factory setting
- - 0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI0 (X07.1) Simulation Terminal eval -
01 DI1 (X07.2) Simulation Terminal eval -