List of parameters
Parameters
1-111
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Dependency: Refer to: r0722
Note: AI: Analog Input
DI: Digital Input
Description: Displays the inverted status of the digital inputs.
Dependency: Refer to: r0722
Note: DI: Digital Input
Description: Sets the debounce time for digital inputs.
Note: The digital inputs are read in cyclically every 2 ms (DI 11, DI 12 every 4 ms).
To debounce the signals, the set debounce time is converted into integer multiple debounce clock cycles Tp (Tp =
p0724 / 2 ms).
DI: Digital Input
Description: Sets the signal source for terminal DO 0 (X05.4)
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: DO: Digital Output
03 DI 3 (X08.2) High Low -
04 DI 4 (X09.4) High Low -
05 DI 5 (X09.2) High Low -
11 DI 11 (X10.3) AI 0 High Low -
12 DI 12 (X10.4) AI 1 High Low -
r0723.0...5 CO/BO: CU digital inputs status inverted / CU DI status inv
CU250D-2_DP_F
CU250D-2_PN_F
Access level: 2 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 1510, 2020, 2030,
2031, 2100, 2120, 2130, 2131, 2132,
2133
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI 0 (X07.4) High Low -
01 DI 1 (X07.2) High Low -
02 DI 2 (X08.4) High Low -
03 DI 3 (X08.2) High Low -
04 DI 4 (X09.4) High Low -
05 DI 5 (X09.2) High Low -
p0724 CU digital inputs debounce time / CU DI t_debounce
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.000 [ms] 20.000 [ms] 4.000 [ms]
p0730 BI: CU signal source for terminal DO 0 / CU S_src DO 0
Access level: 2 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 1510, 2030, 2130
Min Max Factory setting
- - 52.3