Function diagrams
Safety Integrated Extended Functions
2-648
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Fig. 2-62 2855 – F-DI assignment
- 2855 -
Function diagram
87654321
fp_2855_97_55.vsd
Safety Integrated Extended Functions
SINAMICS G120D
12.12.2012 V4.6
F-DI assignment
[2850.8]
F-DI 0
r9722.1
r9722.4
r9722.7
r9720.1
r9720.4
r9720.7
[2820.7]
[2840.5]
SI Mtn integ STW
r9720
r9720
.0
SI Mtn integ stat
r9722
r9722
.0
F-DI assignment
Statically active
Statically inactive
Deselection STO
Deselection SS1
Deselection SLS
Acknowledgement
SS1 active
STO active
SLS active
Internal event
Safe motion
monitoring
SI Motion
SI STO F-DI P1
0 ... 255
p10022 (0)
SI SS1 F-DI P1
0 ... 255
p10023 (0)
SI SLS F-DI P1
0 ... 255
p10026 (0)
SI ackn int evt P1
0 ... 255
p10006 (0)
[2820.1]
[2819.1]
[2819.1]
[2850.8]
F-DI 1
[2850.8]
F-DI 2
SI SDI pos F-DI P1
0 ... 255
p10030 (0)
SI SDI neg F-DI P1
0 ... 255
p10031 (0)
SI SLS F-DI P2
0 ... 255
p10126 (0)
SI SS1 F-DI P2
0 ... 255
p10123 (0)
SI STO F-DI P2
0 ... 255
p10122 (0)
SI SDI pos F-DI P2
0 ... 255
p10130 (0)
SI SDI neg F-DI P2
0 ... 255
p10131 (0)
SI ackn int evt P2
0 ... 255
p10106 (0)
r9720.13
Deselection SDI negative
r9720.12
Deselection SDI positive
r9722.12
[2824.8]
SDI pos active
r9722.13
[2824.8]
SDI neg active
r9722.15
[2823.8]
SSM (n below limit)
[2819.7]
[2819.7]
[2840.4]
[2824.1]
[2824.1]
[2856.1]
[2857.1]