List of parameters
Parameters
1-539
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Description: Sets the PROFIsafe telegram number.
Value: 0: No PROFIsafe telegram selected
30: PROFIsafe standard telegram 30, PZD-1/1
900: PROFIsafe SIEMENS telegram 900, PZD-2/2
998: Compatibility mode (as for firmware version < 4.6)
Note: For p9601.3 = p9801.3 = 1 (PROFIsafe enabled), the following variants exist when parameterizing PROFIsafe tele-
gram 30:
- p9611 = p9811 = 998 and p60022 = 0
- p9611 = p9811 = 998 and p60022 = 30
- p9611 = p9811 = 30 and p60022 = 30
Description: Sets the PROFIsafe telegram number.
Value: 0: No PROFIsafe telegram selected
30: PROFIsafe standard telegram 30, PZD-1/1
998: Compatibility mode (as for firmware version < 4.6)
Note: For p9601.3 = p9801.3 = 1 (PROFIsafe enabled), the following variants exist when parameterizing PROFIsafe tele-
gram 30:
- p9611 = p9811 = 998 and p60022 = 0
- p9611 = p9811 = 998 and p60022 = 30
- p9611 = p9811 = 30 and p60022 = 30
Description: Sets the telegram for the Safety Info Channel (SIC).
The SIC telegram p60122 is attached directly to the PZD telegram p0922/p2079.
Value: 700: Supplementary telegram 700, PZD-0/3
999: Free telegram configuration with BICO
Dependency: Refer to: p0922, p2071, p2079
Note: The clearance to the PZD telegram can be increased using p2071.
After changing p0922/p2079 or p2071, then p60122 must be set again.
The telegram interconnections can only be changed if p60122 and p0922 are both set to 999.
p60022 PROFIsafe telegram selection / Ps telegram_sel
CU240D-2_DP_F
CU240D-2_PN_F
CU250D-2_DP_F
CU250D-2_PN_F
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 998 998
p60022 PROFIsafe telegram selection / Ps telegram_sel
CU240D-2_DP
CU240D-2_PN
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 998 998
p60122 PROFIdrive SIC telegram selection / SIC telegr
CU240D-2_DP_F
CU240D-2_PN_F
CU250D-2_DP_F
CU250D-2_PN_F
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 2423
Min Max Factory setting
700 999 999