List of parameters
Parameters
1-519
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Description: Setting parameter for the interval limit L of instance LVM 1 of the double-sided limiter.
Description: Setting parameter for hysteresis HY of instance LVM 1 of the double-sided limiter.
Description: Display parameter of instance LVM 1 of the double-sided limiter that input quantity X was at least once X > M + L
and X is >= M + L - HY.
Description: Display parameter of instance LVM 1 of the double-sided limiter that the input quantity X lies within the interval.
Description: Display parameter of instance LVM 1 of the double-sided limiter that input quantity X was at least once X < M - L
and X is <= M - L + HY.
p20277 LVM 1 interval limit L / LVM 1 limit L
CU240D-2_DP
CU240D-2_DP_F
CU240D-2_PN
CU240D-2_PN_F
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7270
Min Max Factory setting
-340.28235E36 340.28235E36 0.0000
p20278 LVM 1 hyst HY / LVM 1 hyst HY
CU240D-2_DP
CU240D-2_DP_F
CU240D-2_PN
CU240D-2_PN_F
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7270
Min Max Factory setting
-340.28235E36 340.28235E36 0.0000
r20279 BO: LVM 1 input quantity above interval QU / LVM 1 X above QU
CU240D-2_DP
CU240D-2_DP_F
CU240D-2_PN
CU240D-2_PN_F
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7270
Min Max Factory setting
- - -
r20280 BO: LVM 1 input quantity within interval QM / LVM 1 X within QM
CU240D-2_DP
CU240D-2_DP_F
CU240D-2_PN
CU240D-2_PN_F
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7270
Min Max Factory setting
- - -
r20281 BO: LVM 1 input quantity below interval QL / LVM 1 X below QL
CU240D-2_DP
CU240D-2_DP_F
CU240D-2_PN
CU240D-2_PN_F
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7270
Min Max Factory setting
- - -