Parameters
List of parameters
1-454
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
3: F-DI 2
255: Statically inact
Note: If value = 0:
No terminal assigned, safety function always active.
If value = 255:
No terminal assigned, safety function always inactive.
F-DI: Failsafe Digital Input
SDI: Safe Direction
Description: Sets the fail-safe digital input (F-DI) for the "SDI negative" function.
Value: 0: Statically active
1: F-DI 0
2: F-DI 1
3: F-DI 2
255: Statically inact
Note: If value = 0:
No terminal assigned, safety function always active.
If value = 255:
No terminal assigned, safety function always inactive.
F-DI: Failsafe Digital Input
SDI: Safe Direction
Description: Sets the signals for the drive group specific signal "Safe State".
Description: Sets the signal sources for F-DO 0 (X131.5).
The 6 signal sources in p10042[0...5] are AND'ed and the result is output at F-DO 0.
p10031 SI SDI negative input terminal (processor 1) / SI SDI neg F-DI P1
CU240D-2_DP_F
CU240D-2_PN_F
CU250D-2_DP_F
CU250D-2_PN_F
Access level: 3 Calculated: - Data type: Integer16
Can be changed: C(95) Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 255 0
p10039 SI Safe State signal selection / SI Safe State Sel
CU240D-2_DP_F
CU240D-2_PN_F
CU250D-2_DP_F
CU250D-2_PN_F
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: C(95) Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 2856
Min Max Factory setting
- - 0000 0001 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Power_removed Selected Not selected -
01 SS1_active Selected Not selected -
04 SLS_active Selected Not selected -
05 SDI_pos_active Selected Not selected -
06 SDI_neg_active Selected Not selected -
p10042[0...5] SI F-DO 0 signal sources / SI F-DO 0 S_src
CU240D-2_DP_F
CU240D-2_PN_F
CU250D-2_DP_F
CU250D-2_PN_F
Access level: 3 Calculated: - Data type: Integer16
Can be changed: C(95) Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 2877
Min Max Factory setting
0 13 0