Siemens SINAMICS G120D - p2150[0...n] Hysteresis speed 3; n_hysteresis 3; p2151[0...n] CI: Speed setpoint for messages;signals; n_set for msg; p2152[0...n] Delay for comparison n > n_max; Del n > n_max

Siemens SINAMICS G120D
910 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of parameters
Parameters
1-285
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Dependency: Refer to: r2197
Refer to: A07903
Note: Re bit 00:
Alarm A07903 is output when the bit is set with r2197.7 = 0 (n_set <> n_act).
Re bit 01:
When the bit is set, load monitoring is only carried out in the 1st quadrant as a result of the positive characteristic
parameters (p2182 ... p2190).
Re bit 03:
When the bit is set, r2197 bit 1 and bit 2 are determined via separate hystereses.
Re bit 05: only for synchronous motors
When this bit is set, a change to open-loop speed controlled operation is only possible when the motor is stationary.
Description: Sets the hysteresis speed (bandwidth) for the following signals:
"|n_act| < speed threshold value 3" (BO: r2199.0)
"n_set >= 0" (BO: r2198.5)
"n_act >= 0" (BO: r2197.3)
Dependency: Refer to: p2161, r2197, r2199
Description: Sets the signal source for the speed setpoint for the following messages:
"Speed setpoint - actual value deviation within tolerance t_off" (BO: r2197.7)
"Ramp-up/ramp-down completed" (BO: r2199.5)
"|n_set| < p2161" (BO: r2198.4)
"n_set > 0" (BO: r2198.5)
Dependency: Refer to: r2197, r2198, r2199
Description: Delay time for the comparison of the speed with the maximum speed.
Dependency: Refer to: p1082, r1084, r1087, p2162
p2150[0...n] Hysteresis speed 3 / n_hysteresis 3
Access level: 3 Calculated: p0340 = 1,3,5 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: 3_1 Unit selection: p0505 Func. diagram: 8010
Min Max Factory setting
0.00 [rpm] 300.00 [rpm] 2.00 [rpm]
p2151[0...n] CI: Speed setpoint for messages/signals / n_set for msg
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: p2000 Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 8010
Min Max Factory setting
- - 1170[0]
p2152[0...n] Delay for comparison n > n_max / Del n > n_max
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 [ms] 10000 [ms] 200 [ms]