Siemens SINAMICS G120D - r1045 CO: Mot. potentiometer speed setp. in front of ramp-fct. gen.; Mop n_set bef RFG; p1047[0...n] Motorized potentiometer ramp-up time; Mop ramp­up time; p1048[0...n] Motorized potentiometer ramp-down time; Mop ramp­down time; r1050 CO: Motor. potentiometer setpoint after the ramp-function generator; Mop setp after RFG

Siemens SINAMICS G120D
910 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of parameters
Parameters
1-153
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Note: The setting value (CI: p1044) becomes effective for a 0/1 edge of the setting command (BI: p1043).
Description: Sets the effective setpoint in front of the internal motorized potentiometer ramp-function generator.
Description: Sets the ramp-up time for the internal ramp-function generator for the motorized potentiometer.
The setpoint is changed from zero up to the speed/velocity limit (p1082) within this time (if no initial rounding-off has
been activated).
Dependency: Refer to: p1030, p1048, p1082
Note: When the initial rounding-off is activated (p1030.2) the ramp-up time is correspondingly extended.
Description: Sets the ramp-down time for the internal ramp-function generator for the motorized potentiometer.
The setpoint is changed from the speed/velocity limit (p1082) to zero within this time (if no initial rounding-off has
been activated).
Dependency: Refer to: p1030, p1047, p1082
Note: The deceleration time is extended corresponding to the activated initial rounding-off (p1030.2).
Description: Sets the effective setpoint after the internal motorized potentiometer ramp-function generator.
This setpoint is the output value of the motorized potentiometer and must be appropriately interconnected onwards
(e.g. with the main setpoint).
Dependency: Refer to: p1070
Note: For "With ramp-function generator", after an OFF1, OFF2, OFF3 or for a 0 signal via BI: p0852 (inhibit operation,
suppress pulses) the ramp-function generator output (r1050) is set to the starting value (configuration via p1030.0).
r1045 CO: Mot. potentiometer speed setp. in front of ramp-fct. gen. / Mop n_set bef RFG
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2000 Dyn. index: -
Units group: 3_1 Unit selection: p0505 Func. diagram: 3020
Min Max Factory setting
- [rpm] - [rpm] - [rpm]
p1047[0...n] Motorized potentiometer ramp-up time / Mop ramp-up time
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 3020
Min Max Factory setting
0.000 [s] 1000.000 [s] 10.000 [s]
p1048[0...n] Motorized potentiometer ramp-down time / Mop ramp-down time
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 3020
Min Max Factory setting
0.000 [s] 1000.000 [s] 10.000 [s]
r1050 CO: Motor. potentiometer setpoint after the ramp-function generator /
Mop setp after RFG
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2000 Dyn. index: -
Units group: 3_1 Unit selection: p0505 Func. diagram: 1550, 3020
Min Max Factory setting
- [rpm] - [rpm] - [rpm]