EasyManua.ls Logo

Siemens SINAMICS G120D - Fig. 2-119 6724 - Field weakening controller (PEM, p0300 = 2 xx)

Siemens SINAMICS G120D
910 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Vector control
Function diagrams
2-711
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Fig. 2-119 6724 – Field weakening controller (PEM, p0300 = 2xx)
- 6724 -
Function diagram
87654321
fp_6724_97_53.vsd
Vector control
SINAMICS G120D
12.12.2012 V4.6
Field weakening controller (PEM, p0300 = 2xx)
2
[6640.3]
+
+
+
[6640.1]
[6714.8]
[6731.1]
[6714.8]
[6731.1]
0
+
+
0.9
Min -1
-n
F
n
F
[6721.1]
+
+
100 %
nom
d
L
\
U_set 1
Id_field weaken. Ctrl
PEM: Permanent-magnet synchronous motor
Modulat_depth max [%]
r0073
r0070
Vdc act val [V]
U_output max [Veff]
r0071
Mot U_rated
0 ... 20000 [Veff]
p0304 [D] (0)
Field_ctrl Tn
10 ... 10000 [ms]
p1596 [D] (300)
Mot I_mag_rtd act [Aeff]
r0331 [D]
I_FieldWeak prectr [Aeff]
r1589
r1598
Flux setp total [%]
Flux setp smooth [%]
r1583
Drv filt type mot
0 ... 4
p0230 (0)
Pulse freq setp
2.000 ... 16.000 [kHz]
p1800 [D] (4.000)
Calculation, max. modulation depth
Flux setp T_smth
4 ... 5000 [ms]
p1582 [D] (15)
Mot I_mag_rtd act [Aeff]
r0331 [D]
r0067
I_outp max [Aeff]
r0063
n_act [1/min]
[0]
r1593[0..1]
Field/Fl_ctrl outp [Aeff]
Value range and/or factory setting depend on p0500.
<1>
<1>
<1> <1>
Modulator mode
0 ... 4
p1802 [D] (4)
Modulat depth max
20.0 ... 150.0 [%]
p1803 [D] (106.0)
U_reserve dyn
0.0 ... 150.0 [Veff]
p1574 [D] (10.0)
U_max 1